Technical Data Sheet
FI 72.0239.0320E
Page 107 / 108
(with offset of 100 and no decimal)
Accepted value from 100 à (100+ scale of MDPP2000)
(example: « 234 » for 134 daPa or 13.4 mbar depending of MDPP2000)
1064 (1063)
428 (427)
High alarm threshold of MDPP2000 (number 1)
(with offset of 100 and no decimal)
Accepted value from 100 à (100+ scale of MDPP2000)
(example: « 234 » for 134 daPa or 13.4 mbar depending of MDPP2000)
X
X
1065 (1064)
429 (428)
MDPP2000 Status (number 1)
Bit 0 : =1 if DP order
Bit 1 : =1 if low alarm
Bit 2 : =1 if high alarm
X
1066 (1065)
42A (429)
DP pressure measure from MDPP2000 (number 2)
(with offset of 100 and no decimal)
(example: « 243 » pour 143 daPa or 14.3 mbar depending of MDPP2000
example: « 98 » pour -2 daPa or -0.2 mbar depending of MDPP2000)
DP=(x-100)/10 if unit mbar ; DP=(x-100) if unit daPa
X
...
Cells maintenance requests via MODBUS. A bit per cell. Bit=1 for cell maintenance request
1080 (1079)
438 (437)
Cells maintenance requests
via MODBUS n°1 to 16 (LSB: cell n°1, MSB: cell n°16)
X
X
1081 (1080)
439 (438)
Cells maintenance requests via MODBUS n°17 to 32 (LSB: cell n°17, MSB: cell n°32)
X
X
1082 (1081)
43A (439)
Bit watchdog (exterior towards SFX+)
Used if configuration with communication control
Bit0 : must change of state every 5 seconds
X
X
1083 (1082)
43B (43A)
Bit watchdog (SFX+ towards exterior)
Bit0 : change of state every 5 seconds
X
1084 (1083)
43C (43B)
Reserved (always = 1 ; for gateway link OK)
X
1085 (1084)
43D (43C)
Various flags:
Bit 0 : =0 if there’s at least 1 fault
Bit 1 : =1 if in dust removal cycle and not stopped on cycle
Bit 2 : =1 if manual mode authorized
Bit 3 : =1 if external run order present
Bit 4 : =1 if temperature fault present
Bit 5 to Bit 15 : -
Remark : special programming, non utilisé dans la version standard
X
1086 (1085)
43E (43D)
Flags divers :
Bit 0 : =1 if low batteries
Bit 1 : =1 if at least one link/dialogue fault (with a module or a slave box)
Bit 2 : =1 if at least one SV dust removal electric fault (way cut SV or short circuit)
Bit 3 : =1 if at least one SV dust emission fault
Bit 4 : =1 if general dust emission fault
Bit 5 : =1 if dust emission fault on the last SV (stored until the next SV)
Bit 6 to Bit 15 : -
X
1087 (1086)
43F (43E)
If dust emission fault on the last SV : number of the cell
If not : 0
(stored until the next SV)
X
1088 (1087)
440 (43F)
If dust emission fault on the last SV : number of the way of the cell
If not : 0
(stored until the next SV)
X
1089 (1088)
441 (440)
Online/offline choice
(nb: reserved special programming)
X
X
Fault on cells. 1 bit by cell. Bit=1 if electric fault on a SV of the cell or no consumption pressure fault on a SV of the cell
or dust emission fault on a SV of the cell.
1090 (1089)
442 (441)
Fault on cell n°1 to 16 (LSB: cell n°1, MSB: cell n°16)
X
1091 (1090)
443 (442)
Fault on cell n°17 to 32 (LSB: cell n°17, MSB: cell n°32)
X
Cells in filtration (not in maintenance). 1 bit by cell. Bit=1 if cell is in filtration
(nb: reserved special programming)
1092 (1091)
444 (443)
Cells n°1 to 16 in filtration (LSB :cell n°1, MSB :cell n°16)
X
1093 (1092)
445 (444)
Cells n°17 to 32 in filtration (LSB :cell n°17, MSB :cell n°32)
X
Putting cell in maintenance in action. 1 bit by cell. Bit=1 if putting cell in maintenance in action
(nb: reserved special programming)
1094 (1093)
446 (445)
Cells n°1 to 16 in action (LSB :cell n°1, MSB :cell n°16)
X
1095 (1094)
447 (446)
Cells n°17 to 32 in action (LSB :cell n°17, MSB :cell n°32)
X
Request maintenance cell. 1 bit by cell. Bit=1 when request maintenance
(nb: reserved special programming)
1096 (1095)
448 (447)
Request maintenance cells n°1 to 16 (LSB :cell n°1, MSB :cell n°16)
X
1097 (1096)
449 (448)
Request maintenance cells n°17 to 32 (LSB :cell n°17, MSB :cell n°32)
X
Summary of Contents for SFX+NETWORK
Page 21: ...Technical Data Sheet FI 72 0239 0320E Page 21 108 SIGNALLING...
Page 22: ...Technical Data Sheet FI 72 0239 0320E Page 22 108 CONNECTIONS CONNECTION EXAMPLE...
Page 24: ...Technical Data Sheet FI 72 0239 0320E Page 24 108 CONNECTIONS CONNECTION EXAMPLE...
Page 26: ...Technical Data Sheet FI 72 0239 0320E Page 26 108 CONNECTIONS CONNECTION EXAMPLE...
Page 28: ...Technical Data Sheet FI 72 0239 0320E Page 28 108 CONNECTIONS CONNECTION EXAMPLE...
Page 31: ...Technical Data Sheet FI 72 0239 0320E Page 31 108 CONNECTIONS CONNECTION EXAMPLE...
Page 34: ...Technical Data Sheet FI 72 0239 0320E Page 34 108 CONNECTIONS...
Page 37: ...Technical Data Sheet FI 72 0239 0320E Page 37 108 SFX MODULE POWER CONSUMPTION...
Page 38: ...Technical Data Sheet FI 72 0239 0320E Page 38 108...
Page 85: ...Technical Data Sheet FI 72 0239 0320E Page 85 108...