14
9068.emf
4
5
Protection class IP21:
Cut free the opening on the AC drive cover for the Ethernet cable.
Protection class IP54:
Cut the rubber grommets open to slide the cables through. Should the grommets fold in while
inserting the cable, just draw the cable back a bit to straighten the grommets up. Do not cut the grommet openings wider
than what is necessary for the cables you are using.
NOTE!
To meet the requirements of the enclosure class IP54, the connection between the grommet and the cable must
be tight. Therefore, lead the first bit of the cable out of the grommet straight before letting it bend. If this is not possible,
the tightness of the connection must be ensured with insulation tape or a cable tie.
Remount the AC drive cover.
NOTE!
When planning the cable runs, remember to keep the distance between the Ethernet cable and the motor cable
at a minimum of 30 cm. See figure below.
9265.emf
Ethernet
cable
IP21
IP54