Then connect the cable to its appropriate terminals on Praxi 100 family AC drive standard terminal block, terminals A
and B (A = negative, B = positive). See figure below.
Using the cable clamp included in the delivery of the drive, ground the shield of the RS485 cable to the frame of the AC drive.
NOTE!
This can be done in all drives if there is no difference in PE potentialbetween the drives. However, if there is PE
potential difference then the shieldshould be connected to PE only at one point in the system. The shields of the cables
shall be joint but not connected to several PE points with different potential.
NOTE!
This is only a principle drawing and the actual drive may look different.
Cable clamp
3020.emf