![schmersal Praxi 100 Manual Download Page 42](http://html1.mh-extra.com/html/schmersal/praxi-100/praxi-100_manual_1213191042.webp)
42
Reply Frame:
Reply Frame:
Message Frame:
Table 43.
Table 47.
Table 45.
Exception response:
Table 44.
Table 46.
01
04
04
13
88
09
C4
78
E9
01
84
04
42
C3
01
04
17
70
00
05
34
66
6.5.3 Example 3 - Exception Response
In an exception response, the Slave sets the most-significant bit (MSB) of the function code to 1.
The Slave returns an exception code in the data field.
Command Master - Slave:
Answer Slave - Master:
Address
01 hex
Slave address 1 hex (= 1)
Function
04 hex
Function 4 hex (= 4)
Data
Starting address HI
17 hex
Starting address 1770 hex (= 6000)
Starting address LO
70 hex
No. of registers HI
00 hex
Invalid number of registers 0005 hex (= 5)
No. of registers LO
05 hex
Error Check
CRC HI
34 hex
CRC field 3466 hex (= 13414)
CRC LO
66 hex
Address
01 hex
Slave address 1 hex (= 1)
Function
84 hex
Most significant bit set to 1
Data
Error Code
04 hex
Error code 04 => Slave Device Failure
Error Check
CRC HI
42 hex
CRC field 42C3 hex (= 17091)
CRC LO
C3 hex