29
Defines how many clients can access the server simultaneously.
The Modbus ‘slave address’ field usually used on Modbus Serial Line is replaced by a single byte ‘Unit Identifier’.
When the TCP is used as the communications protocol, the AC drive is addressed by its IP address and broadcast
messages are not possible. In this case, the unit identifier is useless. In the UDP, it is possible to send broadcast
messages and therefore the unit identifier becomes important.
To keep things simple, the unit identifier is checked when using both TCP and UDP. In TCP you can use value 255 (non-
significant) as a unit identifier and send the messages to all slaves with that value.
For Modbus, this value defines the time in which a message must be received (from Client in Modbus TCP/UDP) before
a fieldbus fault is generated. If timeout is set to zero, no fault is created.
See Chapter 6.3.8.
Table 14. Modbus TCP/UDP Monitoring values
5.3.9 Connection Limit
5.3.10 Unit Identifier Number
5.3.11 Communication Timeout
5.3.12 IDMap IDs
Panel Tree
Parameter
Range
Default
ID
Description
P5.9.2.2.1.5
Illegal data values
0…65535
-
2453
See 5.2.12
P5.9.2.2.1.6
Slave device busy
0…65535
-
2454
See 5.2.13
P5.9.2.2.1.7
Memory parity
error
0…65535
-
2455
See 5.2.14
P5.9.2.2.1.8
Slave device failure
0…65535
-
2456
See 5.2.15
P5.9.2.2.1.9
Last fault
response
0
-
2457
See 5.2.16
P5.9.2.2.1.10
Control word
-
hex
2458
See 5.2.17
P5.9.2.2.1.11
Status word
-
hex
2459
See 5.2.18
Summary of Contents for Praxi 100
Page 1: ...Safe solutions for your industry Manual MODBUS Praxi 100...
Page 51: ...51...