Strip about 15 mm of the RS485 cable (see specification in Chapter 3.1) and cut off the
grey cable shield. Remember to do this for both bus cables (except for the last device).
Leave no more than 10 mm of the cable outside the terminal block and strip the cables at
about 5 mm to fit in the terminals. See picture below.
Also strip the cable now at such a distance from the terminal that you can fix it to the frame
with the grounding clamp. Strip the cable at a maximum length of 15 mm. Do not strip the
aluminum cable shield!
9189.emf
10
5
15
mm
9188.emf
4.1.2 Prepare for use Through RS485