32
Address
Range
Purpose
Access
Type
See
R/W
Max
R/W size
0001 - 2000
Praxi Application IDs
16bit
Table 20
RW
30/30
2001 - 2019
FBProcessDataIN
16bit
Table 21
RW
19/19
2051 - 2086
FBProcessDataIN
32bit
Table 21
RW
36/36
2101 - 2119
FBProcessDataOUT
16bit
Table 22
RO
19/0
2151 - 2186
FBProcessDataOUT
32bit
Table 22
RO
36/0
2200 - 10000
Praxi Application IDs
16bit
Table 20
RW
30/30
10501 - 10530
IDMap
16bit
Figure 7
RW
30/30
10601 - 10630
IDMap Read/Write
16bit
Table 23
RW
30/30
10701 - 10760
IDMap Read/Write
32bit
Table 24
RW
30/30
20001 - 40000
Praxi Application IDs
32bit
Table 20
RW
30/30
40001 - 40005
Operation day counter
16bit
Table 26
RO
5/0
40011 - 40012
Operation day counter
32bit
Table 25
RO
2/0
40101 - 40105
Resettable operation
day counter
16bit
Table 28
R, Write 1 to first
index to reset
5/0
40111 - 40112
Resettable operation
day counter
32bit
Table 27
RO
2/0
40201 - 40203
Energy counter
16bit
Table 30
RO
3/0
40211 - 40212
Energy counter
32bit
Table 29
RO
2/0
40301 - 40303
Resettable energy counter
16bit
Table 32
R, Write 1 to first
index to reset
3/0
40311 - 40312
Resettable energy counter
32bit
Table 31
RO
2/0
40401 - 40430
Fault history
16bit
Table 33
RO
30/0
40501
Communication time out
16bit
Table 35
RW
1/1
40511-40568
Fault history with 16 bit
fault codes
16bit
Table 34
RO
30/0
An “input register” in Modbus is a 16-bit value which is read-only. A “holding register” in Modbus is a 16-bit value which
can be both read and written. Holding and input registers are accessed using different function codes, and the address
ranges are different. In Praxi 100 family AC drives, the same information can be accessed as input registers and holding
registers, i.e. input register X refers to the same 16-bit value as the holding register X.
The Modbus registers are mapped to the Praxi 100 family AC drive as follows:
Accessing unsupported values returns the error code “Illegal Data Address”.
Table 19. Defined holding registers
6.3.4 Holding registers and input registers