CO5: System-wide functions (all systems)
If CO5 -> F00 - 1 is indicated, access to the return flow, flow rate and heat capacity set-
tings are locked.
F
Function
WE
Anl
Comment
Function block parameters / Range of values (default)
01
Sensor
initialization
1
1
0
All
CO5-> F01 – 1, F02 – 0, F03 – 0 Pt 1000
CO5-> F01 – 1, F02 – 1, F03 – 0 Ni 1000 DIN
CO5-> F01 – 1, F02 – 1, F03 – 0, CO9-> F01 – 1 Ni 1000-
5k
02
03
04
Summer mode
0
Not Anl
1.5, 1.6,
1.9, 3.5
CO5 -> F04 - 1: Activation of time-controlled summer
mode
Function block parameters:
Start summer mode / 01.01 to 31.12 (01.06)
No. of days until activation / 1 to 3 (2)
Stop summer mode / 01.01 to 31.12 (30.09)
No. of days until deactivation / 1 to 3 (1)
Outdoor temperature limit for summer mode
/
0.0 to 30.0 °C (18.0 °C)
05
Delayed outdoor
temperature
adaptation when
temperature
decreases
0
Not Anl
1.9
CO5 -> F05, 06 - 1:
Function block parameter:
Delay per hour/ 1.0 to 6.0 °C (3.0 °C)
06
Delayed outdoor
temperature
adaptation when
temperature
increases
0
Not Anl
1.9
08
Automatic
summer
time/winter
time
changeover
1
All
09
Frost
protection
program II
1
Not Anl
1.5, 1.6,
1.9, 3.5
CO5 -> F09 - 0: Frost protection program I (restricted
frost protection)
Function block parameter:
Frost protection limit / –15.0 to 3.0 °C (3.0 °C)
CO5 -> F09 - 1: Frost protection program II
Function block parameter:
Frost protection limit / –15.0 to 3.0 °C (3.0 °C)
0
1.5, 1.6,
1.9, 3.5
Summary of Contents for equitherm EQJW126F001
Page 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Page 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Page 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Page 28: ......
Page 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Page 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Page 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Page 49: ......
Page 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Page 58: ......
Page 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Page 63: ......
Page 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Page 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Page 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Page 80: ......
Page 92: ......