Start-up
20
BA_EQJW126F001_EN001
2.2
Changing parameters
Depending on the set system code number and the activated functions, not all
parame- ters listed in the parameter list in the Appendix (–> section 12.2) might be
available. The parameters are grouped by topics:
PA1: Rk1 (Heating circuit 1)
PA2: Not applicable
PA3: Not applicable
PA4: Not applicable
PA5: System-wide parameters
PA6: Communication parameters
1.
Turn the rotary switch to (configuration and parameter
level). Display:
0 0 0 0
2.
Set valid key number [
].
3.
Confirm key number ].
Display:
PA_
4.
Select parameter level [
].
5.
Open parameter level ].
6.
Select parameter [
].
7.
Activate editing mode for the parameter
]. blinks.
8.
Edit the parameter [
].
9.
Confirm the parameter [ ].
To adjust additional parameters in the open parameter level, repeat steps
6 to 9.
10.
Select
End
[
].
11.
Exit parameter level ].
To adjust additional parameters in another parameter level, repeat steps 4 to 9.
12.
Return the rotary switch to normal switch position
(information level).
Summary of Contents for equitherm EQJW126F001
Page 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Page 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Page 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Page 28: ......
Page 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Page 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Page 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Page 49: ......
Page 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Page 58: ......
Page 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Page 63: ......
Page 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Page 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Page 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Page 80: ......
Page 92: ......