Functions of the heating circuit
30
BA_EQJW126F001_EN001
STOP
on the display indicates that there has been a deviation of flow
temperature of more than 5 °C for longer than 30 minutes. The function is
canceled by the controller in such cases. While
STOP
appears on the display, the
controller keeps the flow tempera- ture constant at 25 °C.
A power failure while the drying function is active or when
STOP
appears on the
display automatically leads to the drying function restarting from the beginning.
NOTICE
The function block parameter can only be accessed when the function has
started by de- activating the function block and activating it again.
Functions
WE
Configuration
Underfloor heating
Drying of jointless floors
0
25 °C
5.0 °C
45.0 °C
4
0.0 °C
SToP
CO1 -> F05 - 1
Start temperature / 20 to 60 °C
Temperature rise per day / 0.0 to 10.0 °C
Maximum temperature / 25.0 to 60.0 °C
Maintaining time for max. temperature / 0 to 10
days
Temperature reduction per day / 0.0 to 10.0 °C
STArT,
STArT,
STArT
5.4
Deactivation depending on outdoor temperature
5.4.1
OT deactivation value in rated operation
If the outdoor temperature exceeds the limit
OT deactivation value in rated
operation
, the affected heating circuit is put out of service immediately. The valve is
closed and the pump is switched off after t = 2 x valve transit time. When the
outdoor temperature falls below this value (less 0.5 °C hysteresis), heating operation
is restarted immediately.
With the default settings, this means that, during the warm season, the system is
switched off at an outdoor temperature of 22 °C.
Parameter
WE
Parameter level /
Range
of
values
OT deactivation
value in rated
operation
22.0 °C
PA1
/ 0.0 to 50.0 °C
Summary of Contents for equitherm EQJW126F001
Page 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Page 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Page 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Page 28: ......
Page 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Page 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Page 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Page 49: ......
Page 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Page 58: ......
Page 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Page 63: ......
Page 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Page 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Page 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Page 80: ......
Page 92: ......