42
BA_EQJW126F001_EN001
Electrical connection
6.6
Three-step control
The flow temperature can be controlled using a PI algorithm. The valve reacts to
pulses that the controller sends when a system deviation occurs. The length of the
first pulse, in particular, depends on the extent of the system deviation and the
selected
Proportional gain K
P
(the pulse length increases as K
P
increases). The pulse
and pause lengths change continuously until the system deviation has been
eliminated. The pause length between the single pulses is greatly influenced by the
Reset time T
N
(the pause length increases as T
N
increases).
The
Transit time T
Y
specifies the time required by the valve to travel through the
range of 0 to 100 %.
Function
WE
Configuration
Control mode
1
CO1, 2, 4 -> F12 - 1, Rk_
2.0
KP (proportional gain) / 0.1 to
50.0 120 s Tn (reset time) / 1 to 999 s
0 s
TV (derivative-action time) / Do not change!
45 s
TY (valve transit time) / 5, 10, 15, … , 240 s
6.7
On/off control
The flow temperature can be controlled, for example, by activating and
deactivating a boiler. The controller switches on the boiler when the flow
temperature falls below the set point by T = 0.5 x
hysteresis
. When the set point is
exceeded by T = 0.5 x
hysteresis
, the boiler is switched off again. The greater the
value you choose for
Hysteresis
, the lower the activation/deactivation frequency
will be. By setting the
Minimum ON time
, an activated boiler remains switched on
during this period regardless of the flow tempera- ture fluctuations. Similarly, a
deactivated boiler will remain switched off regardless of the flow temperature
fluctuations if the
Min. OFF time
has been specified.
Function
WE
Configuration
Contro
l
mode
1
CO1, 2, 4 -> F12 - 0
5.0 °C
Hysteresis / 1.0 to 30.0 °C
2 min
Min. ON time / 0 to 10 min
2 min
Min. OFF time / 0 to 10 min
Summary of Contents for equitherm EQJW126F001
Page 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Page 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Page 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Page 28: ......
Page 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Page 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Page 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Page 49: ......
Page 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Page 58: ......
Page 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Page 63: ......
Page 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Page 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Page 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Page 80: ......
Page 92: ......