Functions of the heating circuit
BA_EQJW126F001_EN001
35
5.7
Flash adaptation
To ensure that the controller reacts immediately to room temperature deviations
during rated or reduced operation, the function block setting CO1, 2 -> F09 - 1
needs to be made.
The heating is then always switched off as soon as the room temperature exceeds
the
Day set point
or
Night set point
by 2 °C.
Heating first starts again when the room has cooled off and the room temperature
is 1
°C above the
Set point
. The flow temperature set point is corrected if the
Cycle
time
and
Gain K
P
are set to a value other than 0. The
Cycle time
determines the
intervals at which the flow temperature set point is corrected by 1 °C. A
Gain K
P
set
to a value other than 0 causes a direct increase/decrease in flow temperature set
point when a sudden devia- tion in room temperature arises. A
Gain K
p
setting of
10.0 is recommended.
Note:
Cooling loads, such as drafts or open windows, affect the control process!
Rooms may be temporarily overheated after the cooling load has been
eliminated!
Functions
WE
Configuration
Room sensors RF
0
CO1 -> F01 - 1
Flash adaptation
0
CO1 -> F09 - 1
20 min
Cycle time / 0 to 100 min
0.0
KP (gain) / 0.0 to 25.0
Parameters
WE
Switch position / Range of values
Day set point
Night set point
20.0 °C
15.0 °C
/ 0.0 to 40.0 °C
/ 0.0 to 40.0 °C
5.7.1 Flash adaptation without outdoor sensor
The flow temperature control starts with
Day set point for flow
in rated operation or
with
Night set point for flow
in reduced operation as no set points calculated using
character- istics exist without an outdoor sensor. The
Cycle time
determines the
intervals at which the flow temperature set point is corrected by 1 °C. The heating
is then always switched off as soon as the room temperature exceeds the
Day set
point
or
Night set point
by 2 °C. Heating first starts again when the room has
cooled off and the room temperature is 1
Summary of Contents for equitherm EQJW126F001
Page 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Page 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Page 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Page 28: ......
Page 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Page 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Page 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Page 49: ......
Page 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Page 58: ......
Page 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Page 63: ......
Page 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Page 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Page 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Page 80: ......
Page 92: ......