26
BA_EQJW126F001_EN001
Functions of the heating circuit
5.1.2
Four-point characteristic
The four-point characteristic allows you to define your own heating characteristic. It is de-
fined by four points for the outdoor temperature, flow temperature, reduced flow temperature
and return flow temperature. The 'Max. flow temperature' and 'Min. flow temperature' pa-
rameters mark the upper and lower limits of the flow temperature.
t
VL
[˚C]
100
t
VLmax
90
P1 to P4 Points 1 to 4
80
t
VL
Flow temperature
70
P1
t
A
Outdoor temperature
60
P2
- - - min Min. flow temperature
50
- - - max Max. flow temperature
40
P3
––––––––– Four-point characteristic
30
P4
–––––– Reduced four-point
t
VLmin
20
t
A
characteristic
10
20 15 10
5
0
–5 –10 –15 –20
[˚C]
Fig. 4:
Four-point characteristic
Note:
−
The 'Day set point' and 'Night set point' parameters are no longer available when
the four-point characteristic has been selected, provided no additional functions
(e.g.
optimization
,
flash adaptation
) have been selected.
−
The four-point characteristic function can only be activated when the
adaptation
function is not active (CO1, 2 > F08 - 0).
Functions
WE
Configuration
Adaptation
Four-point characteristic
0
0
CO1, 2 > F08 - 0
CO1, 2 > F11 - 1
Parameters
WE
Parameters: value range
Outdoor temperature
Point 1
–15.0 °C
PA1, 2 > P05:–50.0 to 50.0 °C
Point 2
–5.0 °C
Point 3
5.0 °C
Point 4
15.0 °C
Summary of Contents for equitherm EQJW126F001
Page 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Page 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Page 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Page 28: ......
Page 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Page 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Page 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Page 49: ......
Page 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Page 58: ......
Page 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Page 63: ......
Page 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Page 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Page 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Page 80: ......
Page 92: ......