Functions of the heating circuit
BA_EQJW126F001_EN001
27
Outside the times-of-use, reduced set points are used for control:
The reduced flow set point is calculated as the difference between the adjusted
values for
Day set point
(rated room temperature) and
Night set point
(reduced
room tempera- ture).
The
Max. flow temperature
and
Min. flow temperature
parameters mark the
upper and lower limits of the flow temperature. A separate gradient characteristic
can be selected for the limitation of the return flow temperature.
Examples for adjusting the characteristic:
Old building, radiator design 90/70:
Gradient approx. 1.8
New building, radiator design 70/55:
Gradient approx. 1.4
New building, radiator design 55/45:
Gradient approx. 1.0
Underfloor heating depending on arrangement: Gradient smaller than
0.5
Note:
Particularly for control operation without room sensor, the room
temperatures set for day (Day set point) and night (Night set point) only become
effective satisfactorily when the heating characteristic has been adapted to the
building/heating surface layout.
Function
WE
Configuration
Four-point characteristic
0
CO1 -> F11 - 0
Parameters
WE
Switch position / Range of values
Day set point
Night set point
20.0 °C
15.0 °C
/ 0.0 to 40.0 °C
/ 0.0 to 40.0 °C
Parameters
WE
Parameter level /
Range
of
values
Gradient, flow
1.8*
PA1 / 0.2 to 3.2
Level, flow
0.0 °C
PA1 / –30.0 to 30.0 °C
Min. flow temperature
20.0 °C
PA1 / 5.0 to 130.0 °C
Max. flow temperature
90.0 °C*
PA1 / 5.0 to 130.0 °C
* With CO1 -> F05 - 1, the following applies: Gradient, flow / 0.2 to 1.0 (1.0)
Max. flow temperature / 5.0 to 50.0 °C (50.0 °C)
Summary of Contents for equitherm EQJW126F001
Page 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Page 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Page 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Page 28: ......
Page 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Page 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Page 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Page 49: ......
Page 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Page 58: ......
Page 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Page 63: ......
Page 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Page 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Page 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Page 80: ......
Page 92: ......