18
BA_EQJW126F001_EN001
Start-up
2
Start-up
The modifications of the controller configuration and parameter settings
described in this section can only be performed after the valid key number has
been entered.
The valid key number for initial start-up can be found on page 86. To avoid
unautho- rized use of the key number, remove the page or make the key number
unreadable. In addition, it is possible to enter a new, customized key number (–>
section 7.15).
2.1
Activating and deactivating functions
A function is activated or deactivated in the associated function block. The
numbers 0 to 24 in the top row of the display represent the respective function
block numbers. When a configuration level is opened, the activated function
blocks are indicated by a black square on the right-hand side below the
function block number. For more details on function blocks, refer to section 12.1.
The functions are grouped by topics:
CO1: Rk1 (Heating circuit 1)
CO2: Not applicable
CO3: Not applicable
CO4: Not applicable
CO5: System-wide functions
CO6: Modbus communication
Proceed as follows:
1. Turn the rotary switch to (configuration and parameter
level). Set valid key number [
].
3.
Confirm key number ].
Display:
PA_
4.
Select configuration level [
].
5.
Open configuration level ].
Summary of Contents for equitherm EQJW126F001
Page 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Page 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Page 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Page 28: ......
Page 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Page 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Page 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Page 49: ......
Page 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Page 58: ......
Page 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Page 63: ......
Page 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Page 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Page 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Page 80: ......
Page 92: ......