BA_EQJW126F001_EN001
59
Installation
8.5
Memory module
The use of a memory module (0440210010) is particularly useful to transfer all data
from one EQJW126 Controller to several other EQJW126 Controllers.
The memory module is plugged into the RJ-45 jack at the side. Once the module
has been connected, “73 SP“ is displayed. If the memory module already contains
data from a different EQJW126 Controller, turn the rotary pushbutton until “SP 73"
is displayed.
Pressing the rotary pushbutton to confirm “73 SP“ causes the controller
settings to be transferred to the memory module.
Pressing the rotary pushbutton to confirm “SP 73“ causes the saved
controller set- tings to be transferred from the memory module to the
controller.
During the data transfer, the bars on the display indicate the progress. When the
trans- fer was successful, “I.O.“ is displayed. After that, the connection between
controller and memory module can be terminated.
8.6
Data logging
A data logging module (0440210009) saves the following controller data every two
min utes:
Temperatures measured by the sensors
Control signals [%]
Switching states of the pump outputs
Error status register and its archive data
Access to the controller settings
The data logging module is connected to the RJ-45 jack at the side of the controller.
The controller starts to write over the oldest data as soon the memory of the data
log- ging module is full after approximately eight days. The current memory
capacity of the data logging module can be read in the extended information
level under
Info 2
as the second in the sequence (range of values: 0 to 6035).
Directly after inserting the data logging module, data can be first read after the
first scanning cycle has been performed.
The data log viewer software allows the data to be viewed in graph format. The
USB converter 3 (0440210007) is re quired to connect the data logging mod ule
to a com puter. The data log viewer software is supplied with the USB converter
3.
Summary of Contents for equitherm EQJW126F001
Page 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Page 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Page 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Page 28: ......
Page 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Page 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Page 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Page 49: ......
Page 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Page 58: ......
Page 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Page 63: ......
Page 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Page 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Page 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Page 80: ......
Page 92: ......