BA_EQJW126F001_EN001
23
Manual operation
3
Manual operation
Switch to manual mode to configure all outputs, refer to wiring diagram (-> section
NOTICE
The frost protection does not function when the controller is in manual mode.
Proceed as follows:
1.
Turn the rotary switch to
(manual level).
2.
Select output depending on the control circuit
(
): POS_ Positioning value in percent
UP_
Activation/deactivation of the circulation pump (heating)
3.
Confirm the output
]. The display blinks.
4.
Change positioning value/switching state [
].
5.
Confirm setting ].
The modified values remain active as long as the controller is in manual mode.
6.
Return the rotary switch to normal switch position
(information
level). The manual mode is deactivated.
Note:
The outputs of the controller are not affected by simply turning the rotary
switch to
(manual level). You have to actually enter a positioning value or
activate/deacti-
vate the pumps to configure the outputs
Summary of Contents for equitherm EQJW126F001
Page 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Page 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Page 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Page 28: ......
Page 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Page 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Page 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Page 49: ......
Page 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Page 58: ......
Page 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Page 63: ......
Page 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Page 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Page 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Page 80: ......
Page 92: ......