Functions of the heating circuit
40
BA_EQJW126F001_EN001
Cooling control without outdoor sensor
When the cooling control function is activated in a control circuit without outdoor
sen- sor, only the adjustment limits for the day and night set points at the rotary
switch as well as the
Base point for return flow temperature
can be adjusted in
PA1 and/or PA2.
Functions
WE
Configuration
Outdoor sensor AF
Cooling control
0
CO1 -> F04 - 0
CO1 -> F04 - 1
Parameters
WE
Rotary switch / Range of values
Day set point
Night set point
20.0 °C
15.0 °C
/ 0.0 to 40.0 °C
/ 0.0 to 40.0 °C
Parameters
WE
Parameter level / Range of values
Min. flow temperature
20 °C
PA1 / 5.0 to 130.0 °C
Max. flow temperature
90 °C
PA1 / 5.0 to 130.0 °C
Base point of return flow
65 °C
PA1 / 5.0 to 90.0 °C
temperature
Summary of Contents for equitherm EQJW126F001
Page 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Page 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Page 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Page 28: ......
Page 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Page 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Page 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Page 49: ......
Page 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Page 58: ......
Page 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Page 63: ......
Page 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Page 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Page 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Page 80: ......
Page 92: ......