Appendix
70
BA_EQJW126F001_EN001
12.2
Parameter lists
PA1: Parameters Rk1 (heating circuit 1)
Display
Parameter designation
Range of values
(default) Gradient, flow
0.2 to 3.2 (1.8)
(with CO1 -> F05 - 1: 0.2 to 1.0 (1.0) applies)
Level (parallel shift)
–30.0 to 30.0 °C (0.0 °C)
Min. flow temperature
5.0 to 130.0 °C (20.0 °C)
Max. flow temperature
5.0 to 130.0 °C (90.0 °C)
(with CO1, 2, 3 -> F05 - 1: 5.0 to 50.0 °C (50.0 °C) applies)