Commissioning with Terminal
PR 5610 Installation Manual
116 Sartorius
5.2.6 Fieldbus
parameter
Calling up mask
Set fieldbus configuration
is from sub-menu
Configuration
by pressing key [F].
PR1713 Rel. 03.12 20.05.2004 09:05
Fieldbus Configuration
PR1721 protocol :Interbus-S
IBS cycles/25ms :10
Interbus-S
Calculate actualization interval:
1000 / (15 + number of bytes+ 0.3 x number
of slaves)
PR1713 Rel. 03.12 20.05.2004 09:05
Fieldbus Configuration
PR1721 protocol :Profibus-DP
Profibus-DP address : 1
Profibus-DP
Enter [1 ... 126] for Profibus-DP address
PR1713 Rel. 03.12 20.05.2004 09:05
Fieldbus Configuration
PR1721 protocol :DeviceNet
DeviceNet baudrate : 250k
DeviceNet MAC-ID : 1
DeviceNet
Select baudrate [125k or 250k or 500k]
Enter [1 ... 62] for DeviceNet address
PR1713 Rel. 03.12 20.05.2004 09:05
Fieldbus Configuration
PR1721 protocol :
Scale-interface......:enabled
All protocols
Scale-interface: enabled for using standard
interface fieldbus - PR5610 with 8 bytes.
Disabled if IEC 61131 application program is
handling the fieldbus.
After parameter entry the instrument makes a warm start, in order to initialize the PR 1721 module in the unit.