Record time
Indoor
temperature
Transformer
temperature
Cell cabinet
temperature
Run
frequency
Output
voltage
Output
current
Fault type
&description
Table 8-2 VFD Run Record
8.5.2 Regular maintenance
●
The recommended maintenance interval is six months. When in dust environment, the filter replacement cycle
can be shortened to one week.
●
Clean-up work: filters, transformer cabinets, cell cabinets.
●
Tighten work: transformer in and out cables, power cells in and out cables, control cables, signal cables.
8.5.3 Spare cell maintenance
●
Make sure that spare cell the two fiber base plugs TX/ RX is tight to prevent dust pollution.
●
Run the spare cell every 6 months.