Figure 4-5 Terminal row above interface board (remote start/stop mode is pulse mode )
Figure 4-4 Terminal row above theinterface board (remote start/stop mode is level mode)
● Switch value input all require passive null nodes, when several switch values are in the same
connection, among which the 24V+2 can share common wiring.
● Interface board remote reset signal and cabinet door reset button have the same function: when
VFD has no heavy fault, only reset the HMI, and this will not cause other effects on the system (eg.
Resetting when VFD is running will not cause VFD stop); when VFD has heavy fault and remove the
fault, then reset the control system, VFD will return to normal.