109
Line
Name
Nature
Mod
address
PLC
address
Parameter
description
Parameter description
72
Parameter
combination 5
R/W
47H
40072
Bit
Name
0
1
15
14
13
12
11
10
9
8
7
6
5
4
Control status
Debugging
mode
Normal status
3
Stop mode
Deceleration
stop
Free stop
2
Master slave
mode
Master mode
Slave mode
1
Master-slave
set
Invalid
Valid
0
73
Parameter
combination 6
R/W
48H
40073
Byte
Name
Byte interpretation
High byte
VFD mode
1.Common use for async motor
2.Vector control for async motor
3.Common use for sync motor
4.vector control for sync motor
5.Sensorless vector control for async motor
6.Sensorless vector control for sync motor
Start mode
0:normal start 1:speed start 2:torque start
3:position start 4:rotor start 5:no-load test
6:parameter identification
74 VFD input voltage R/W
49H
40074
380~10000V
75 VFD rated voltage R/W
4AH
40075
380~10000V
76 VFD rated current R/W
4BH
40076
31.0~1600.0A
77
Input current
proportion
R/W
4CH
40077
100-2000
78
Switch phase-
lock angle
R/W
4DH
40078
0.5-3
79
Motor group
R/W
4EH
40079
0:first group 1:second group 2:third group 3:fourth group
80
Motor rated
voltage
R/W
4FH
40080
380~10000V
81
Motor rated
current
R/W
50H
40081
0.1~1600.0A
82
Motor rated
frequency
R/W
51H
40082
5.00~80.00Hz