60
SANTERNO
USER MANUAL
Parameter name
Description
Value
Unit
Default
value
Change
Max. feedback current
When there is analog feedback, the Max. value of
the site feedback current signal, corresponding to
100% of the feedback quantity
Notes: When the analog feedback is a voltage
signal, the maximum value of the feedback voltage
should also be adjusted by this parameter.
10.00~25.00
mA
20.00
○
Min. feedback current
When there is analog feedback, the Max. value
of the site feedback current signal, corresponding
to 0% of the feedback quantity
Notes: When the analog feedback is a voltage
signal , the feedback voltage minimum should
also be adjusted by this parameter
0.00~8.00
mA
4.00
○
Process close loop
proportional coefficient
The operation mode is closed loop operation, the
setting of proportional coefficient of PI control
0.5~20.00
No
10
◎
Process close loop
integral time
The operation mode is closed loop operation and
the integral time is controlled by PI control
0.01~20.00
Min
10.00
◎
Analog set filter
cardinality
Analogue set, set the filter coefficient of analog
signal
0~50
No
0
○
VFD address
The address assigned to the VFD when the upper
computer is in communication with the frequency
converter must be consistent with the address of
the upper computer
1~31
No
31
○
Cooling mode
Setting of Heat dissipation mode of VFDwhen the
temperature of VFD cabinet is too high
0 : Air cooling
1 : Water
No
0
◎
Ventilation filter
cleaning
If there is too much dust in the ventilation screen,
Whether set the ventilation filter network cleaning
alarm reminding
0 : Ignore
1 : Remind
No
0
○
Time dedusting time
Ventilation filter cleaning set to remind, this
parameter is valid
15~3000
Day
0
○
Fan stop time
The time that allows the fan continuing to work
after the VFD stops running
0~30
Min
0
○
Cabinet door light/
heavy fault selection
When door alarms, two types of alarms: light fault
and heavy fault
0: light fault
1: heavy fault
No
0
○