5.4 Appendix
Table 5-1 Function parameter setting
“○”: It indicates that the setting value of the function can be changed in the stop or running state of VFD.
“
◎
”: It indicates that the setting value of the function cannot be changed in the running state of VFD.
Parameter
name
Description
Value
Unit
Default
value
Change
Parameter
setting
Whether it is allowed to set the parameters of VFD or not
After disabled, except this parameter, table 5-1, table
5-2, table 5-3, table 5-4, table 5-5 and table 5-6 internal
parameters can not be modified
0
:
Disable
1
:
Enable
No
0
◎
Restore
factory
setting
Whether restore factory setting or not
0
:
Disable
1
:
Enable
No
0
◎
Analog set
loss
Whether the set frequency is allowed to maintain the
original set value after the set loss, valid when the set
mode is set to analog set
Enable : Maintain the set frequency after the loss; if the
reset operation, the set frequency becomes the Min.
frequency
Disable : The set frequency changes to the Min.
frequency after the loss
0
:
Disable
1
:
Enable
No
1
◎
MV loss
quick break
When high voltage lost, it is allowed to report MV loss;
when it is disable, VFD in standby no heavy fault and show
MV ready, when running it reports MV loss (according to
shielding time delay)
0
:
Disable
1
:
Enable
No
0
◎
MV loss
auto restart
The time of MV power loss is within the time delay of
power loss shield (less than or equal to), whether to allow
the VFD auto restore to the running state before the
power loss. Before the MV loss, the system was running,
valid when MV loss quick break enable, and the start
mode is speed start
0
:
Disable
1
:
Enable
No
1
◎
Remote
start/stop
mode
Setting of the remote start/stop trigger mode, valid when
control mode is remote control.
Level mode : PLC-XS1T-1, 10 terminals are defined to
level forward start/stop; XS1T-1, 9 terminals are defined
to level reverse start/stop
Pulse mode : PLC-XS1T-1, 10 terminals are defined to
pulse start; XS1T-1, 9 terminals are defined to pulse stop
0
:
Pulse mode
1
:
Level mode
No
1
◎
VFD
reverse
Whether the VFD is allowed to reverse or not,
see section 5.3.6
0
:
Disable
1
:
Enable
No
0
◎