58
SANTERNO
USER MANUAL
Parameter name
Description
Value
Unit
Default
value
Change
Analog output 1
Set for PLC-XS18T~11, M3 terminal custom analog output
signal content
0
:
Output
frequency
1
:
Output
current
2
:
Cell cabinet
temperature
3
:
Excitation
current
4
:
Output
power
5
:
Output
power factor
No
0
◎
Analog output 2
Set for PLC-XS18T~12, M4 terminal custom analog output
signal content
No
1
◎
Analog feedback
Line loss
Whether the set parameter is allowed to maintain the original
set value after loss, it’s valid when the set mode is set to
analog set
Enable: After the loss, the set parameter keep the original set
value.
Disable : After the loss, the set parameter change to 0
0
:
Disable
1
:
Enable
No
1
◎
Set control mode
by remote
Whether to allow the control mode by remote of VFD. After
allowed, there are two control modes : local control (remote
control enable open of the interface board) and remote control
(remote control enable close of the interface board)
0
:
Disable
1
:
Enable
No
0
◎
Motor parameter
control
Whether to set the motor parameter
0
:
Disable
1
:
Enable
No
0
◎
Motor parameter
location selection
Choose the motor parameters when one VFD drives multi-
motors.
0
:
Group 1
1
:
Group 2
2
:
Group 3
3
:
Group 4
No
0
◎
Switch given
selection
When the VFD given mode is the switch given,
the setting of a given switch position
0
:
Speed
section 3
1
:
Speed
section 7
No
0
○
Grid/VFD switch
Whether it’s allow to realize the function of "sync transfer
switch", i.e. transfer between grid side running and the VFD
running, see 6.3
0
:
Disable
1
:
Enable
No
1
○
Control mode
Set the control mode of VFD start/stop, see 5.3.3
0
:
Local
1
:
Upper
2
:
Remote
No
0
○
Set mode
Set the set mode of VFD frequency, see 5.3.4
0
:
Local
1
:
Analog
2
:
DI
3
:
Upper
No
0
○
Running mode
Set the running mode of VFD, see 5.3.1
0
:
Open loop
1
:
Close loop
No
0
○