40
SALICRU
10. . PRODUCT SPECIFICATION
10.1. APPLICABLE STANDARDS
Item
Normative reference
General safety requirements for UPS used in operator
access areas
EN-IEC62040-1-1/AS 62040-1-1
Electromagnetic compatibility (EMC) requirements for UPS
EN-IEC62040-2/AS 62040-2 (C3)
Method of specifying the performance and test
requirements of UPS
EN-IEC62040-3/AS 62040-3 (VFI SS 111)
Table 24.
Compliance with European and International
Standards
10.2. ENVIRONMENTAL CHARACTERISTICS
Item
Unit
Requirements
Acoustic noise level
dB
65dB @ 100% carga, 62dB @ 45% carga
at 1 meter
dB
65dB @ 100% load, 62dB @ 45% load
Altitude of Operation
m
≤1000,load derated 1% per 100m from 1000m and 2000m
Relative Humidity
%
0-95,non condensing
Operating Temperature
Celsius
0-40,Battery life is halved for every 10°C increase above 20°C
UPS Storage Temperature
Celsius
-40-70
Table 25.
Environmental Characteristics
10.3. MECHANICAL CHARACTERISTIC
Item
Unit
150/30
300/30
Mechanical Dimension
W×D×H
mm
600*1100*2000
Weight
kg
220
Color
N/A
Black
Protection Level (IEC60529)
N/A
IP20
Table 26.
Mechanical Characteristics for Cabinet
Item
Unit
Parameter
Mechanical Dimension, W×D×H
mm
460×790×134
Weight
kg
34
Table 27.
Mechanical Characteristics for Power Module