8. OPERATIONS
8.1. UPS START-UP
8.1.1. Start from Normal Mode
The UPS must be started up by commissioning engineer after
the completeness of installation. The steps below must be fol-
lowed:
1.
Ensure all the external circuit breakers are open.
2.
Close the input external circuit breakers and the system
starts initializing. If the system has dual inputs close both
of the breakers.
3.
The LCD in front of the cabinet is lit up. The system enters
the home page, as shown in Fig. 36.
4.
Notice the energy bar in the home page, and pay attention
to the LED indicators. The rectifier flashes indicating the
rectifier is starting up. The LED indicators are listed below
in Table 20.
Indicator
Status
Indicator
Status
Rectifier
green flashing
Inverter
off
Battery
red
Load
off
Bypass
off
Status
red
Table 20.
Rectifier starting up
5.
After 30S, the rectifier indicator goes steady green, pre-
senting the finishing of rectification and bypass static
switch closes then the inverter is starting up. The LED indi-
cators are listed below in Table. 21.
Indicator
Status
Indicator
Status
Rectifier
green
Inverter
green flashing
Battery
red
Load
green
Bypass
green
Status
red
Table 21.
Inverter starting up
6.
The UPS transfers from the bypass to inverter after the in-
verter goes normal. The LED indicators are listed below in
Table 22.
Indicator
Status
Indicator
Status
Rectifier
green
Inverter
green
Battery
red
Load
green
Bypass
off
Status
red
Table 22.
Supplying the load
7.
The UPS is in Normal Mode. Close the battery circuit
breakers and the UPS starts charging the battery. The LED
indicators are listed below in Table 23.
Indicator
Status
Indicator
Status
Rectifier
green
Inverter
green
Battery
green
Load
green
Bypass
off
Status
green
Table 23.
Normal mode
8.
Close the output circuit breaker for the load and it finishes
the starting up for the UPS.
Note:
•
When the system starts, the stored setting will be loaded.
•
Users can browse all incidents during the process of the
starting up by checking the menu Log.
•
Information of each power module can be viewed by the
keys in the front of it.
8.1.2. Start from Battery Mode
The start for battery model is referring to battery cold start. The
steps for the start-up are as follows:
1.
Confirm the battery is correctly connected; close the ex-
ternal battery circuit breakers.
2.
Press the red button for the battery cold start (See Fig. 50).
The system is than powered by the battery.
1
2
1- Manual Bypass
2- Battery Cold Start
Fig. 50.
The position of the battery cold start button.
3.
After that, the system is starting up following steps 3 in
section 8.1.1 and the system transfers to battery mode in
30S.
4.
Close the external output power supply isolation to supply
the load, and the system is working on battery model.
ADAPT
UNINTERRUPTIBLE POWER SUPPLY
USER'S MANUAL