30
SALICRU
Sq.
LCD Display
Explanation
39
Battery Maintenance-Set
Battery Maintenance Starts
40
Batt Maintenance OK-Set
Battery maintenance succeeds
41
Batt Maintenance Fail-Set
Battery maintenance fails
42
Module Inserted-Set
N# Power Module joins the
system
43
Module Exit-Set
N# Power Module quits the
system.
44
Rectifier Fail-Set
N# Power Module Rectifier
Fails
45
Rectifier Fail-Clear
Incident above disappears
46
Inverter Fail-Set
N# Power Module Inverter Fail
47
Inverter Fail-Clear
Incident above disappears
48
Rectifier Over Temp.-Set
N# Power Module Rectifier
Over Temperature
49
Rectifier Over Temp.-Clear
Incident above disappears
50
Fan Fail-Set
N# Power Module Fan Fail
51
Fan Fail-Clear
Incident above disappears
52
Output Overload-Set
N# Power Module Output Over
Load
53
Output Overload-Clear
Incident above disappears
54
Inverter Overload Tout-Set
N# Power Module Inverter
Over Load Timeout
55
INV Overload Tout-Clear
Incident above disappears
56
Inverter Over Temp.-Set
N# Power Module Inverter
Over Temperature
57
Inverter Over Temp.-Clear
Incident above disappears
58
On UPS Inhibited-Set
Inhibit system transfer from
bypass to UPS (inverter)
59
On UPS Inhibited-Clear
Incident above disappears
60
Manual Transfer Byp-Set
Transfer to bypass manually
61
Manual Transfer Byp-Set
Cancel to bypass manually
62
Esc Manual Bypass-Set
Escape transfer to bypass
manually command
63
Battery Volt Low-Set
Battery Voltage Low
64
Battery Volt Low-Clear
Incident above disappears
65
Battery Reverse-Set
Battery pole (positive and
negative are reverse)
66
Battery Reverse-Clear
Incident above disappears
67
Inverter Protect-Set
N# Power Module Inverter
Protect ( Inverter Voltage
Abnormal or Power Back feed
to DC Bus)
68
Inverter Protect-Clear
Incident above disappears
69
Input Neutral Lost-Set
Input Grid Neutral Lost
70
Bypass Fan Fail-Set
Bypass Module Fan Fail
71
Bypass Fan Fail-Clear
Incident above disappears
72
Manual Shutdown-Set
N# Power Module Manually
Shutdown
73
Manual Boost Charge-Set
Manually Battery Boost
Charge
74
Manual Float Charge-Set
Manually Battery Float Charge
Sq.
LCD Display
Explanation
75
UPS Locked-Set
Inhibit to shut down the UPS
76
Parallel Cable Error-Set
Parallel cable in error
77
Parallel Cable Error-Clear
Incident above disappears
78
Lost N+X Redundant
Lost N+X Redundant
79
N+X Redundant Lost-Clear
Incident above disappears
80
EOD Sys Inhibited
System is inhibited to supply
after the battery is EOD (end of
discharging)
81
Power Share Fail-Set
Power share is not in balance
82
Power Share Fail-Clear
Incident above disappears
83
Input Volt Detect Fail-Set
Input Voltage is abnormal
84
Input Volt Detect Fail-Clear
Incident above disappears
85
Battery Volt Detect Fail-Set
Battery Voltage is abnormal
86
Batt Volt Detect Fail-Clear
Incident above disappears
87
Output Volt Fail-Set
Output Voltage is abnormal
88
Output Volt Fail-Clear
Incident above disappears
89
Outlet Temp. Error-Set
Outlet Temperature is
abnormal
90
Outlet Temp. Error-Clear
Incident above disappears
91
Input Curr Unbalance-Set
Input current is not balance
92
Input Curr Unbalance-Clear
Incident above disappears
93
DC Bus Over Volt-Set
DC bus over Voltage
94
DC Bus Over Volt-Clear
Incident above disappears
95
REC Soft Start Fail-Set
Rectifier soft start fails
96
REC Soft Start Fail-Clear
Incident above disappears
97
Relay Connect Fail-Set
Relay in open circuit
98
Relay Connect Fail-Clear
Incident above disappears
99
Relay Short Circuit-Set
Relay shorted
100
Relay Short Circuit-Clear
Incident above disappears
101
No Inlet Temp. Sensor-Set
The inlet temperature sensor is
not connected or abnormal
102
No Inlet Temp Sensor-Clear
Incident above disappears
103
No Outlet Temp. Sensor-Set The Outlet temperature sensor
is not connected or abnormal
104
No Outlet TmpSensor-Clear
Incident above disappears
105
Inlet Over Temp.-Set
Inlet over temperature
106
Inlet Over Temp.-Clear
Incident above disappears
Table 19.
List for incidents
Note:
Different colors of the words represent different level of inci-
dents: (a)Green, an event occurs: (b)Grey, the event occurs then
clears: (c)Yellow, warning occurs: (d) Red, faults happen.