21
Codes
Description
16
Main abnormal
18
Bypass phase sequence fault
20
Bypass voltage abnormal
28
Bypass Over-track frequency
30
Over-transferring-time
32
Output shorted
34
EOD of battery
38
Battery test fail
41
Battery maintenance fail
47
Rectifier fail
49
Inverter fail
51
Rectifier over temperature
53
Fan fail
55
Output overload
57
Output overload time out
59
Inverter over temperature
61
UPS inverter Inhibited
65
Low battery
67
Battery phase reversed
69
Inverter protected
71
Neutral disconnected
74
Module shut down manual
81
Battery or charger fail
83
Lost N+X redundancy
85
EOD system inhibited
93
Inverter data CAN fail
95
Data CAN fail
97
Power share fail
109
Inverter bridge open
111
Temperature difference over limit
113
Input current unbalanced
115
DC bus over voltage
117
Rectifier soft start fail
119
Relay open
121
Relay shorted
127
Transfer to inverter manually
Tabla 12.
codes for faults and warnings
7.4. LCD PANEL FOR CBINET
The structure of operator control and display panel for cabinet
is shown in Fig. 33.
1
2
3
4
6
7
8
9
5
BYP
INV
MUTE
10
11
12
1-LCD touch screen
2: EPO switch
3: Audible Alarm (Buzzer)
4: Status indicator
5: Bypass indicator
6: Rectifier indicator
7: Inverter indicator
8: Load indicator
9: Battery indicator
10: Bypass transfer
11: Inverter transfer
12: Mute
Fig. 33.
Control and display panel for cabinet
The LCD panel for cabinet is divided into three functional areas:
LED indicator: control and operation keys and LCD touch screen.
7.4.1. LED Indicator
There are 6 LEDs on the panel to indicate the operating status and
fault. The description of indicators is shown in Table 13.
Indicator
State
Description
Rectifier
indicator
Steady green
Rectifier normal for all modules
Flashing
green
Rectifier normal for at least one module,
mains normal
Steady red
Rectifier fault
Flashing red
Mains abnormal for at least one module
Off
Rectifier not operating
Battery
indicator
Steady green
Load supplied by inverter
Flashing
green
Inverter on, start, synchronization or
standby (ECO mode) for at least one
module
Steady red
System output not supplied by inverter,
inverter fault for at least one module.
Flashing red
System output supplied by inverter,
inverter fault for at least one module.
Off
Battery and battery converter normal,
battery not charging
ADAPT
UNINTERRUPTIBLE POWER SUPPLY
USER'S MANUAL