
35
8.3. BATTERY MAINTENANCE
If the battery is not in use for a long time, it is necessary to test
the condition of the battery. Two methods are provided:
1.
Discharging by manual. Enter the menu Operate, as is
shown in Fig.52 and touch the icon “Battery maintenance”
, the system transfers into the Battery mode for
discharging. The system will stop charging when the bat-
tery is 20% in capacity or in low voltage. Users can stop
the discharging by touching the “Stop Test” icon
.
Fig. 52.
Battery maintenance
2.
Auto discharging. The system can maintenance the battery
automatically when the setting is done. The setting proce-
dures are as follows.
(a) Enable battery auto discharge. Enter the “CONFIGURE”
page of the menu Setting, tick the “Battery Auto Discharge”
and confirm (This needs to be done by factory).
(b) Setting period for battery auto discharge. Enter the
“BATTERY “page of the Setting (See Fig.54), Set the period
time in the item “Auto Maintenance Discharge Period” and
confirm.
6480
Fig. 53.
Setting period for battery auto discharge
Warning:
The load for the auto maintenance discharge should be 20%-
100%, if not, the system will not start the process automati-
cally.
8.4. EPO
The EPO button located in the operator control and display
panel (with cover to avoid disoperation, see Fig.55) is designed
to switch off the UPS in emergency conditions (e.g., fire, flood,
etc.).To achieve this, just press the EPO button, and the system
will turn off the rectifier, inverter and stop powering the load
immediately (including the inverter and bypass output), and the
battery stops charging or discharging.
If the input utility is present, the UPS control circuit will remain
active; however, the output will be turned off. To completely
isolate the UPS, users need to open the external mains input
supply to the UPS
Warning:
When the EPO is triggered, the load is not powered by the UPS.
Be careful to use the EPO function.
1
1- EPO BUTTON
Fig. 54.
EPO
ADAPT
UNINTERRUPTIBLE POWER SUPPLY
USER'S MANUAL