Parameters in the file para.ini: advanced configuration
SAGEM RT3000
87
Datei 8115AD002-Total.doc
Datei gespeichert
24.04.04 13:23 von EDV/ORGA
Druckzeit 24.04.04,
18:17
Status Release
Section:
DEVICE_ACCESS
Meaning Parameter Permitted
Values
Factory
Setting
Activate power report
POWER_REPORT
YES, NO
NO
Telephone number for
sending power report to
POWER_REPORT_NR 100
digits
16.4
Select Port for Incoming SMS
Can be configured by SMS (see page 82)
Can be configured by FTP (see page 83)
Can be configured by DTMF (see page 80)
You can select where an incoming SMS should be routed to.
Section:
DEVICE_ACCESS
SMS_PORT=A to the Telephone port (Landline SMS capable telephone set required)
SMS_PORT=B to the Telephone port (Landline SMS capable telephone set required)
SMS_PORT=C to the PC interface (Default)
Section:
DEVICE_ACCESS
Meaning
Parameter
Permitted Values Factory Setting
Switch incoming
SMS to PC-SMS or
to analogue SMS
SMS_PORT
A, B, C
C
16.5
Select Baudrate for Debug-RS232
Can be configured by SMS (see page 82)
Can be configured by FTP (see page 83)
The baudrate of the Debug-Interface can be configured. The Debug-Interface is not part
of a standard product.
[SERVICE_IF]
BAUDRATE=57600
Section:
SERVICE_IF
Meaning
Parameter
Permitted Values Factory Setting
Baudrate for debug
RS232
BAUDRATE
300, 600, 1200,
2400, 4800, 9600,
19200, 38400,
57600, 115200
57600