Model 3095FB Multivariable Transmitter with Modbus Protocol
Modbus Protocol Guide
Page 47 of 79
6.2 Damping
A damping factor can also be entered for each process variable. The damping will smooth the
process variable reading when there are rapid input variations. The following damping values
(in seconds) are available. The underlined value is the default.
If the new damping value, sent by the host, is not one of the valid options, the closest damping
value will be selected. Only values of 0 to 30 seconds will be accepted by the 3095FB. If the
value is outside of this range a Modbus exception Illegal Data Value (03) will be returned.
0.108
0.216
0.432
0.864
1.728
3.456
6.912
13.824
27.648
Table 6-3 Damping
Modbus Access
DESCRIPTION
Address
Address
Type
Attributes
Functional
Area
Data / Control
0441,
0442
FP register
R/W, WP
Damping
DP damping
0447,
0448
FP register
R/W, WP
SP damping
0453,
0454
FP register
R/W, WP
PT damping
*Attributes: R/W = Read/Write, RO = Read Only, WP = Write Protected
**These registers are available at multiple Modbus addresses (see Section 2.3 located in
the
Modbus Protocol Guide
)