Model 3095FB Multivariable Transmitter with Modbus Protocol
Modbus Protocol Guide
Page 29 of 79
0029
Holding
register
R/W, WP
Materials
of Con-
struction
number of remote seals (U8)
1
2
250
251
252
One Seal
Two Seal
Not Used
None
Unknown
0030,
0031
Holding
register
R/W, WP
transmitter
info
user-entered date (U24)
day/month/year
i.e. April 26, 1996 = 0x001a, 0x0460
0032-
0035
ASCII
R/W, WP
user-entered tag (U8x8)
0036-
0043
ASCII
R/W, WP
user-entered descriptor(U8x16)
0044-
0059
ASCII
R/W, WP
user entered message (U8x32)
*Attributes: R/W = Read/Write, RO = Read Only, WP = Write Protected
**These registers are available at multiple Modbus addresses (see Section 2.3
located in the
Modbus Protocol Guide
)
Table 4-1 Transmitter Info
Modbus Access
DESCRIPTION
Address
Address
Type
Attributes
Functional
Area
Data / Control