Reference Manual
00809-0100-4738, Rev DA
May 2006
Rosemount 3095FB
2-6
NOTE
Most transmitters are calibrated in the horizontal position. Mounting the
transmitter in any other position will shift the zero point to the equivalent
amount of liquid head caused by the varied mounting position. To reset zero
point, refer to “Sensor Trim” on page 4-16.
Mounting Bolts
The following guidelines have been established to ensure a tight flange,
adapter, or manifold seal. Use only bolts supplied with the transmitter or sold
by Rosemount Inc. as a spare part to the Rosemount 3095FB transmitter.
The Rosemount 3095FB is shipped with the Coplanar flange installed with
four 1.75-inch flange bolts. The following bolts also are supplied to facilitate
other mounting configurations:
•
Four 2.25-inch manifold/flange bolts for mounting the Coplanar flange
on a three-valve manifold. In this configuration, the 1.75-inch bolts may
be used to mount the flange adapters to the process connection side of
the manifold.
•
(Optional) If flange adapters are ordered, four 2.88-inch flange/adapter
bolts for mounting the flange adapters to the Coplanar flange.
Figure 2-3 shows the optional mounting bracket and mounting configurations.
Stainless steel bolts supplied by Rosemount Inc. are coated with a lubricant to
ease installation. Carbon steel bolts do not require lubrication. No additional
lubricant should be applied when installing either type of bolt. Bolts supplied
by Rosemount Inc. are identified by their head markings: