Reference Manual
00809-0100-4738, Rev DA
May 2006
Rosemount 3095FB
4-8
Setup > Units…
This screen defines the units of measure for the differential pressure, static
pressure, and temperature measurements.
Units of measure are available per Table 4-1.
Table 4-1. Units of Measure
Figure 4-5. Units of Measure Screen
Setup > Damping…
The 3095FB has electronic damping that can change the response time of the
transmitter to smooth the process variable reading when there are rapid input
variations. Different damping values can be entered for the DP, SP, and PT
process variables. Available damping values are shown in Table 4-2.
High damping values filter out process noise, but response time is decreased.
Low damping values increase response time, but process noise can also be
detected. The factory default damping value is 0.864.
To change the damping value, simply enter new values, and click
Set Values
.
If a new value is selected that is not available, the 3095FB automatically
selects the closest damping value.
Table 4-2. Damping
Differential Pressure
Static Pressure
Temperature
InH
2
0 - 60°F
PSI
°F
InH
2
0 - 68°F
kPa
°C
Pa
MPA
kPa
Available Damping Values (in seconds)
0.108
0.216
0.432
0.864
1.728
3.456
6.912
13.824
27.648