Model 3095FB Multivariable Transmitter with Modbus Protocol
Modbus Protocol Guide
Page 36 of 79
5.3.1.1 Method 1: Define the Endpoints
The host can configure the scaled integers just by defining the endpoints (x
1
,y
1
and x
2
,y
2
)
for the line shown Figure 5-1 .
The 3095FB will reject endpoints that do not conform to the following limits.
The values for x
1
and x
2
should be configured for the current unit codes. If the host
changes unit codes after the scaled integers are configured using Method 1, the values for
x
1
and x
2
will be changed to reflect the new unit codes.
Table 5-6 Limits for Defining Endpoints
Variable
Valid Range
Type
Description
x
1
LRL < x
1
< (x
2
- min_span)
F32
Minimum Measured Value
x
2
(x
1
+ min_span) < x
2
< URL
F32
Maximum Measured Value
y
1
0 < y
1
< y
2
U16
Minimum Scaled Integer
y
2
y
1
< y
2
< 65534
U16
Maximum Scaled Integer