background image

Accura 2300/2350 User Guide 

Chapter 3 Accura 2350 Operation/Setup 

 

  2011 Rootech Inc. All Rights Reserved 

Page 125 

 

(4) Wiring/load direction: 

 VLL (Left load, Line-to-line wiring) 

Single-phase  module  is  installed  and  line-to-line  wiring  is  selected  to  support  line-to-line  single-phase 

measurement.

   

 

 

 

 

 

4.1) Single-phase measurement 

Select line-to-line wiring. 

 

 

Setup range [Line-to-line single-phase single-hole connection]

 

 

 

 

 

 

 

 

 

 

Summary of Contents for Accura 2300 Front

Page 1: ...ACCURA 2300 2350 Distribution Panel Digital Power Meter Power Measuring Module Actually makes possible enterprise energy management User Guide English Revision 1 30 2018 9 17...

Page 2: ...ura 2350 3P 250A 105 TM 3P 105 Accura 2350 1P 250A 105 TM 1P 105 Accura 2350 3P 125A 90 TM 3P 90 Accura 2350 1P 125A 60 TM 1P 60 Accura 2350 3P 100A 75 TM 3P 75L Accura 2350 1P 100A 50 TM 1P 50L Accur...

Page 3: ...core Single phase Single hole Power Measuring Module Accura 2350 3PSC 250A 105 Accura 2350 1PSC 250A 105 Accura 2350 1PSCSH 800A Accura 2350 3PSC 125A 90 Accura 2350 1PSC 125A 60 Accura 2350 1PSCSH 63...

Page 4: ...Special purpose Module Accura 2350 GAS Accura 2350 GW Accura 2350 TEMP Accura 2350 DO Accura 2350 IDC Accura 2350 VDC Accura 2350 DCM...

Page 5: ...direct voltage or current Installation Considerations Installation and operation of Accura 2300 2350 should be performed only by qualified competent personnel that have appropriate training and exper...

Page 6: ...mers to obtain the latest specifications of device before giving orders to confirm that the information being relied on by the customer is up to date In the absence of written agreement to the contrar...

Page 7: ...not meet the warranties then the original purchaser s sole remedy and Rootech s sole obligation or liability shall be at Rootech s option to repair replace or refund the price paid for that product Li...

Page 8: ...ginal purchaser It is the original purchaser s responsibility to determine the suitability of any product and associated documentation for its purposes The original purchaser acknowledges that 100 up...

Page 9: ...hanged button Revision 1 13 2014 05 23 Single diagram modified Revision 1 14 2015 01 29 Rear side plate modified Revision 1 15 2015 05 21 Standard compliance added and logo image updated Revision 1 20...

Page 10: ...9 Accura 2350 1PSC Split core Single phase Power Measuring Module Mounting 64 Accura 2350 1PSCSH Split core Single phase Single hole Power Measuring Module Mounting 69 Step 2 Accura 2300 Wiring 73 Acc...

Page 11: ...Mode 127 LED Display 127 Button Operation 127 Display Mode 129 Front Display 129 Accura 2350 Module ID Selection 131 Display Full Screen 132 Voltage Current Power Energy 133 Voltage Frequency 133 Cur...

Page 12: ...te 185 Step 3 Accura 2300 Ethernet Setup 188 Chapter 5 Measurement Description 189 General Measurement Factor 189 Measurement Event Factor 191 Measurement for Voltage Connection 192 3 Phase 4 Wire 192...

Page 13: ...Accura 2300 2350 User Guide Contents 2011 Rootech Inc All Rights Reserved Page 13 Reliability 215 APPENDIX D Ordering Information 216...

Page 14: ...ra 2300 Rear Dimension 35 Fig 2 17 Accura 2350 3P Three phase Power Measuring Module Dimension 36 Fig 2 18 TM 3P Three phase Terminal Dimension 36 Fig 2 19 Accura 2350 1P Single phase Power Measuring...

Page 15: ...ion 77 Fig 2 54 Single phase 2 wire 1PT Connection 77 Fig 2 55 Accura 2300 Digital Input Output Channel 78 Fig 2 56 Digital Input 79 Fig 2 57 DC Relay application 80 Fig 2 58 AC Relay application 80 F...

Page 16: ...y VL12 Secondary V13 141 Fig 4 21 1 phase 2 wire connection 1P2W PT Primary VL12 Secondary V1N 141 Fig 4 22 Dip Event Setup 3 phase 4 wire 146 Fig 4 23 Dip Event Setup 3 phase 3 wire 146 Fig 4 24 Swel...

Page 17: ...veral Accura 2350s on RS 485 communication and displays measurements of only one Accura 2350 selected on its LCD screen This provides energy management supervisor with the power quality information of...

Page 18: ...t the maximum minimum occurrence time time stamp This includes information of measurement parameters that fluctuate instantaneously with respect to the aggregation interval thus enabling accurate tren...

Page 19: ...ion Live line Installation by Split core Structure applied only to split core power measuring module Accura 2350 3PSC 1PSC 1PSCSH split core three single phase power measuring module makes it possible...

Page 20: ...ssion Management by Reduction of High Energy Cost Accura 2300 2350 provides power quality information which enables management of energy use power facility operation and high efficiency device analysi...

Page 21: ...measuring rating 100A 85g Accura 2350 1P 60A 50 Current measuring rating 60A 85g Accura 2350 1P 50A 35 Current measuring rating 50A 74g Accura 2350 1P 30A 35 Current measuring rating 30A 74g Single ph...

Page 22: ...350 3P CT5A 75 or Accura 2350 3PSC CT5A 90 using external CT secondary rating 5A should be used 6 Split core single phase single hole power measuring modules can be used in three phases by installing...

Page 23: ...telephone line should be minimum 0 128mm2 26 AWG It is recommended that distance from power line is 5mm or more so that interference caused by noisy power line will not occur 3 Ethernet communication...

Page 24: ...with device Core conductor of 6C telephone line should be minimum 0 128mm2 26 AWG It is recommended that distance from power line is 5mm or more so that interference caused by noisy power line will no...

Page 25: ...42 69Hz Voltage 0 2 RD Current 0 2 RD 0 5 RD 16 Power Power factor IEC62053 22 Class 0 5S 0 2S 17 Demand Peak demand Predicted demand 4 5 Maximum minimum after reset Maximum 5 minimum 5 average 5 in a...

Page 26: ...on LCD screen of Accura 2300 It is available by only communication 6 Only for communication with a number of Accura 2350s connected by 6C telephone line 7 Maximum 15 Accura 2350s can be connected to...

Page 27: ...e phase Accura 2350 1PSH 50A 35 50mA 200mA 60A single hole Accura 2350 1PSH 30A 35 30mA 120mA 36A Measurement Sampling cycle for harmonic analysis 64 Sampling cycle for RMS and power calculation 32 Me...

Page 28: ...3 22 Class 0 5S Class 0 2S 8 Communication RS 485 3 2 ports RJ12A RJ12B 4 Combination Connected with Accura 2300 or 2350 by 6C telephone line 5 6 General UL certification UL61010 1 CE certification EN...

Page 29: ...l Three phase TM 3P 105 Accura 2350 3P 250A 105 connection TM 3P 90 Accura 2350 3P 125A 90 connection TM 3P 75L Accura 2350 3P 100A 75 connection TM 3P 75 Accura 2350 3P 60A 75 connection TM 3P 105 LB...

Page 30: ...following guidelines Item Acceptable Range Position Indoor use Operating temperature 20 to 70 C 4 to 158 Safety temperature 1 20 to 65 C 4 to 149 Storage temperature 40 to 85 C 40 to 185 Operating hu...

Page 31: ...and safety precautions presented in this guide Danger Power up after the voltage and current wiring is completed Meter Overview Fig 2 1 Accura 2300 Front Fig 2 2 Accura 2300 Side Fig 2 3 Accura 2300 R...

Page 32: ...1P Power Measuring Module Three phase power measuring module Single phase power measuring module Fig 2 5 Accura 2350 3PSC 1PSC 1PSCSH Split core Power Measuring Module Split core three phase power mea...

Page 33: ...6C telephone line 3m x 2 75cm x 1 Fig 2 7 Accura 2350 3P Three phase Power Measuring Module Component Accura 2350 3P Mounting plate Two screws 6C telephone line 10cm x 1 Fig 2 8 Accura 2350 1P Single...

Page 34: ...10 Accura 2350 1PSC Split core Single phase Power Measuring Module Component Accura 2350 1PSC Mounting plate Two screws 6C telephone line 20cm x 1 10cm x 1 Fig 2 11 Accura 2350 1PSCSH Split core Sing...

Page 35: ...2300 2350 User Guide Chapter 2 Installation 2011 Rootech Inc All Rights Reserved Page 35 Dimension Fig 2 14 Accura 2300 Front Dimension Fig 2 15 Accura 2300 Side Dimension Fig 2 16 Accura 2300 Rear Di...

Page 36: ...Rootech Inc All Rights Reserved Fig 2 17 Accura 2350 3P Three phase Power Measuring Module Dimension Accura 2350 3P 250A 105 Accura 2350 3P 125A 90 Accura 2350 3P 100A 60A CT5A 75 Fig 2 18 TM 3P Three...

Page 37: ...ra 2350 1P Single phase Power Measuring Module Dimension Accura 2350 1P 250A 105 1 Accura 2350 1P 125A 60 Accura 2350 1P 100A 60A 50 Accura 2350 1P 50A 30A 35 1 Accura 2350 1P 250A 105 is a single pha...

Page 38: ...ghts Reserved TM 1P 50L TM 1P 50 Fig 2 21 Accura 2350 1PSH PSH Single phase Single hole Power Measuring Module Dimension Accura 2350 1PSH 50A 30A 35 Fig 2 22 Accura 2350 3PSC Split core Three phase Po...

Page 39: ...of B phase middle hole is slightly larger than that of A and C phase considering the external 2 CT connection Fig 2 23 Accura 2350 1PSC Split core Single phase Power Measuring Module Dimension Accura...

Page 40: ...Accura 2300 2350 User Guide Page 40 2011 Rootech Inc All Rights Reserved Fig 2 24 Accura 2350 1PSCSH Split core Single phase Single hole Power Measuring Module Dimension Accura 2350 1PSCSH 800A Accura...

Page 41: ...a 2350 1P 30A 35 50 0 x 34 8 x 60 0 mm Single phase single hole Accura 2350 1PSH 50A 35 50 0 x 34 8 x 60 0 mm power measuring module Accura 2350 1PSH 30A 35 50 0 x 34 8 x 60 0 mm Single phase terminal...

Page 42: ...ith device Core conductor of 6C telephone line should be minimum 0 128mm2 26 AWG It is recommended that distance from power line is 5mm or more so that interference caused by noisy power line will not...

Page 43: ...e phases only by installing two modules on phase A and phase C 1 Packaged with device Core conductor of 6C telephone line should be minimum 0 128mm2 26 AWG It is recommended that distance from power l...

Page 44: ...ep 1 Mounting Accura 2300 Mounting Accura 2300 is mounted on front of distribution panel or switchgear panel Fit the meter into the cutout 145mm x 112mm Cover back of the meter with mounting plate Com...

Page 45: ...the mounting plate by tightening the screws diagonally Attach Accura 2350 3P three phase power measuring module to the mounting plate Combine Accura 2350 3P with the three phase terminal Secure the th...

Page 46: ...0 2350 User Guide Page 46 2011 Rootech Inc All Rights Reserved Fig 2 29 Accura 2350 3P Three Phase Terminal Panel Perforation Application Model Accura 2350 3P 250A 105 TM 3P 105 Application Model Accu...

Page 47: ...Accura 2300 2350 User Guide Chapter 2 Installation 2011 Rootech Inc All Rights Reserved Page 47 Application Model Accura 2350 3P 125A 90 TM 3P 90 Application Model Accura 2350 3P 125A 90 TM 3P 90 LB...

Page 48: ...Chapter 2 Installation Accura 2300 2350 User Guide Page 48 2011 Rootech Inc All Rights Reserved Application Model Accura 2350 3P 100A 75 TM 3P 75L Application Model Accura 2350 3P 60A 75 TM 3P 75...

Page 49: ...uide Chapter 2 Installation 2011 Rootech Inc All Rights Reserved Page 49 Application Model Accura 2350 3P 100A 75 Accura 2350 3P 60A 75 TM 3P 75 LB Application Model Accura 2350 3P 100A 75 Accura 2350...

Page 50: ...2300 2350 User Guide Page 50 2011 Rootech Inc All Rights Reserved Fig 2 30 Accura 2350 3P Mounting Plate Terminal Panel Perforation Accura 2350 3P 250A 105 TM 3P 105 Accura 2350 3P 125A 90 TM 3P 90 Ac...

Page 51: ...Accura 2300 2350 User Guide Chapter 2 Installation 2011 Rootech Inc All Rights Reserved Page 51 Accura 2350 3P 60A CT5A 75 TM 3P 75...

Page 52: ...the mounting plate by tightening the screws diagonally Attach Accura 2350 1P Single phase power measuring module to the mounting plate Combine Accura 2350 1P with the three phase terminal Secure the t...

Page 53: ...pter 2 Installation 2011 Rootech Inc All Rights Reserved Page 53 Fig 2 32 Accura 2350 1P Single Phase Terminal Panel Perforation Application Model Accura 2350 1P 250A 105 TM 1P 105 Application Model A...

Page 54: ...nstallation Accura 2300 2350 User Guide Page 54 2011 Rootech Inc All Rights Reserved Application Model Accura 2350 1P 125A 60 TM 1P 60 LB Application Model Accura 2350 1P 100A 50 Accura 2350 1P 60A 50...

Page 55: ...Guide Chapter 2 Installation 2011 Rootech Inc All Rights Reserved Page 55 Application Model Accura 2350 1P 100A 50 Accura 2350 1P 60A 50 TM 1P 50 Application Model Accura 2350 1P 100A 50 Accura 2350...

Page 56: ...Chapter 2 Installation Accura 2300 2350 User Guide Page 56 2011 Rootech Inc All Rights Reserved Application Model Accura 2350 1P 100A 50 Accura 2350 1P 60A 50 TM 1P 50L LB...

Page 57: ...apter 2 Installation 2011 Rootech Inc All Rights Reserved Page 57 Fig 2 33 Accura 2350 1P Mounting Plate Terminal Panel Perforation Accura 2350 1P 250A 105 TM 1P 105 Accura 2350 1P 125A 60 TM 1P 60 Ac...

Page 58: ...Installation Accura 2300 2350 User Guide Page 58 2011 Rootech Inc All Rights Reserved Accura 2350 1P 60A 50 TM 1P 50 Accura 2350 1P 50A 35 Accura 2350 1P 30A 35 Accura 2350 1PSH 50A 35 Accura 2350 1P...

Page 59: ...g New Installation Place the mounting plate on the inner panel Secure the mounting plate by tightening the screws diagonally Slide attach Accura 2350 3PSC split core three phase power measuring module...

Page 60: ...350 User Guide Page 60 2011 Rootech Inc All Rights Reserved Fig 2 35 Accura 2350 3PSC Split core Three phase Power Measuring Module Panel Perforation Application Model Accura 2350 3PSC 250A 105 Applic...

Page 61: ...Accura 2300 2350 User Guide Chapter 2 Installation 2011 Rootech Inc All Rights Reserved Page 61 Application Model Accura 2350 3PSC 60A 75 Application Model Accura 2350 3PSC CT5A 90...

Page 62: ...on Accura 2300 2350 User Guide Page 62 2011 Rootech Inc All Rights Reserved Fig 2 36 Accura 2350 3PSC Split core Mounting Plate Panel Perforation Accura 2350 3PSC 250A 105 Accura 2350 3PSC 125A 90 Acc...

Page 63: ...ge 63 Remodeling Installation Combine the upper part of Accura 2350 3PSC to the lower part Secure Accura 2350 3PSC with a cable tie 200x4 8mm for remodeling installation Fig 2 37 Accura 2350 3PSC Spli...

Page 64: ...g New Installation Place the mounting plate on the inner panel Secure the mounting plate by tightening the screws diagonally Slide attach Accura 2350 1PSC Split core single phase power measuring modul...

Page 65: ...Installation 2011 Rootech Inc All Rights Reserved Page 65 Fig 2 39 Accura 2350 1PSC Split core Single phase Power Measuring Module Panel Perforation Application Model Accura 2350 1PSC 250A 105 Applic...

Page 66: ...Chapter 2 Installation Accura 2300 2350 User Guide Page 66 2011 Rootech Inc All Rights Reserved Application Model Accura 2350 1PSC 60A 50...

Page 67: ...r Guide Chapter 2 Installation 2011 Rootech Inc All Rights Reserved Page 67 Fig 2 40 Accura 2350 1PSC Split core Mounting Plate Panel Perforation Accura 2350 1PSC 250A 105 Accura 2350 1PSC 125A 60 Acc...

Page 68: ...erved Remodeling Installation Combine the upper part of Accura 2350 1PSC to the lower part Secure Accura 2350 1PSC with a cable tie 200x4 8mm for remodeling installation Fig 2 41 Accura 2350 1PSC Spli...

Page 69: ...wer Measuring Module Mounting New Installation Place the mounting plate on the inner panel Secure the mounting plate by tightening the screws diagonally Slide attach Accura 2350 1PSCSH split core sing...

Page 70: ...er Guide Page 70 2011 Rootech Inc All Rights Reserved Fig 2 43 Accura 2350 1PSCSH Split core Power Measuring Module Panel Perforation Application Model Accura 2350 1PSCSH 800A Application Model Accura...

Page 71: ...00 2350 User Guide Chapter 2 Installation 2011 Rootech Inc All Rights Reserved Page 71 Fig 2 44 Accura 2350 1PSCSH Split core Mounting Plate Panel Perforation Accura 2350 1PSCSH 800A Accura 2350 1PSC...

Page 72: ...ed Remodeling Installation Combine the upper part of Accura 2350 1PSCSH to the lower part Secure Accura 2350 1PSCSH with a cable tie 200x4 8mm for remodeling installation Fig 2 45 Accura 2350 1PSCSH S...

Page 73: ...C 660V direct L L Line to Line Frequency range 50 60Hz 42 69Hz Voltage connection 3 Phase 4 Wire 3 Phase 3 Wire 1 Phase 3 Wire 1 Phase 2 Wire connection Burden 0 02VA phase 220V Withstand voltage AC 2...

Page 74: ...74 2011 Rootech Inc All Rights Reserved Three phase 4 Wire Connection Fig 2 47 3 phase 4 wire Direct Connection Note Select 3P4W in Voltage connection setup screen Fig 2 48 3 phase 4 wire 3PT Connect...

Page 75: ...Rootech Inc All Rights Reserved Page 75 3 phase 3 wire Connection Fig 2 49 3 phase 3 wire Direct Connection Note Select 3P3W in Voltage connection setup screen Fig 2 50 Three phase 3 wire 2PT Connect...

Page 76: ...setup screen Be sure to connect to V1 V3 and VN terminals The neutral line is the middle point between Line 1 and Line 2 and should be connected to the VN terminal Fig 2 52 Single phase 3 wire 2PT Co...

Page 77: ...Select 1P2W in Voltage connection setup screen Be sure to connect to V1 and VN terminals Line to neutral phase voltage or Line1 Line2 line voltage can be connected Fig 2 54 Single phase 2 wire 1PT Con...

Page 78: ...annels with RS 485 channel Refer to ordering information Fig 2 55 Accura 2300 Digital Input Output Channel Digital Input 2 Channels Channel 1 Channel 2 Connector name DI1 DI2 Ground 1 DIG DIG 1 Ground...

Page 79: ...n AC 2 000V for 1 minute Maximum rating AC 250V 5A DC 110V 0 3A DC 30V 5A 1 Action of digital output is as follows Output Type Command 3 Operation Latch 1 Maintain closed contact 0 Maintain open conta...

Page 80: ...s normal If Reverse polarity is selected the operation of the closed contact and the open contact is reversed Note For latch or pulse type selection refer to Chapter 4 Setup Mode Digital Input Output...

Page 81: ...350 1P 50A 35 50mA 200mA 60A Accura 2350 1P 30A 35 30mA 120mA 36A Single phase Accura 2350 1PSH 50A 35 50mA 200mA 60A single hole Accura 2350 1PSH 30A 35 30mA 120mA 36A Impedance Not applicable becaus...

Page 82: ...ructure Frequency range 42 69Hz Hole size Model Size Weight through hole Three phase Accura 2350 3PSC 250A 105 23 0 x 31 7 mm 428g Accura 2350 3PSC 125A 90 18 2 x 31 7 mm 390g Accura 2350 3PSC 60A 75...

Page 83: ...ura 2350 3PSC 250A 105 Accura 2350 3PSC 125A 90 Accura 2350 3PSC 60A 75 Accura 2350 3PSC CT5A 90 1 Fig 2 60 Three phase 4 wire 3 wire 3CT Through hole Wiring Application Model Three phase Module Accur...

Page 84: ...Module Accura 2350 3P CT5A 75 1 Accura 2350 3PSC CT5A 90 1 1 If rating current exceeds 250A Accura 2350 3P CT5A 75 using external CT secondary rating 5A should be used Note Current through hole wirin...

Page 85: ...Accura 2350 1P 30A 35 Split core Single phase Module Accura 2350 1PSC 250A 105 Accura 2350 1PSC 125A 60 Accura 2350 1PSC 60A 50 Fig 2 63 Single phase LL Line to line Through hole Wiring Application Mo...

Page 86: ...g range Model Minimum Measurement Measuring Range Accuracy guaranteed 1 Accura 2350 1PSCSH 800A 0 80A 3 20A 960A Accura 2350 1PSCSH 630A 0 63A 2 52A 756A Accura 2350 1PSCSH 400A 0 40A 1 60A 480A Imped...

Page 87: ...Application Model Split core Single phase Single hole Module Accura 2350 1PSCSH 800A Accura 2350 1PSCSH 630A Accura 2350 1PSCSH 400A Fig 2 65 Two Module Group Device for 3P3W connection Application Mo...

Page 88: ...Wiring Application Model Split core Single hole Module Accura 2350 1PSCSH 800A Accura 2350 1PSCSH 630A Accura 2350 1PSCSH 400A Fig 2 67 Single phase LL Line to line Single hole Module Through hole Wi...

Page 89: ...of Communication Installation Front panel Accura 2300 Distribution panel digital power meter Incoming feeder Accura 2350 3P CT5A 75 1 Three phase power measuring module Branch load Accura 2350 3P Thre...

Page 90: ...0 using external CT secondary rating 5A should be used 2 Packaged with device Core conductor of 6C telephone line should be minimum 0 128mm2 26 AWG It is recommended that distance from power line is 5...

Page 91: ...20 Accura 2300s can be daisy chained and can be wired with star and ring connection also The standard protocol Modbus TCP is supported for measurement data transmission Accura 2300 supports RSTP Rapid...

Page 92: ...of distribution boards or switchgear boards is an environment that emits a large amount of electromagnetic waves due to electric power lines This can seriously affect the quality of Ethernet communic...

Page 93: ...cation terminal Fig 2 71 Accura 2300 RS 485 Communication Option RS 485 1 Port Item Description Port name Ta TRX Tb TRX Sh Shield Connector type Screw type terminal Pluggable Protocol Modbus RTU Baud...

Page 94: ...00 300V Withstand voltage AC 2 500V RMS 60Hz for 1 minute Compliance Pollution degree 2 Power consumption Max 20VA Depends on the number of Accura 2350 connected Inrush current Peak 25A duration 2msec...

Page 95: ...on If there is no button input for 10 seconds it automatically switches to the display mode Button Operation Button Description Display Mode Automatically displays measured values sequentially Setup M...

Page 96: ...90 using external CT secondary rating 5A should be used 2 Indicates CT secondary current input range 3 Three phase module meets 0 2 RD current accuracy and IEC62053 22 Class 0 5S power energy accuracy...

Page 97: ...Power C Phase Current Power 3 Phase Avg Current 3 Phase Total Power 3 Phase Total Energy Leakage Current 1 1 Leakage current measurement is supported by installing an external ZCT voltage type and con...

Page 98: ...nt measurement setup screen Note If there is no button operation for 10 seconds in setup mode it automatically returns to display mode If there is no button operation for 25 seconds in setup change mo...

Page 99: ...Inc All Rights Reserved Page 99 Phase Sequence Load Direction Setup Item Description ac default Through hole sequence A B C Load direction ca Through hole sequence C B A Load direction ac Through hol...

Page 100: ...elected single phase is measured When the voltage connection is 1P2W or 1P3W three phase power measuring module automatically performs the measurement according to the 1P2W 1P3W setup so this load con...

Page 101: ...hase Selection Setup This is a setup screen for selecting wiring image when Load Connection is set to 2Ld or 1Ld 1 When Load Connection setup menu is set to 2Ld thC through hole Connection 2Ld 2 load...

Page 102: ...Rights Reserved 2 When Load Connection setup menu is set to 1Ld thC through hole Connection 1Ld Single load Item Description a b line to line AB 1 load b c line to line BC 1 load c a line to line CA 1...

Page 103: ...rent 6000A Secondary Rating Current 5A CT ratio 6000A 5A 1200 CT Ratio 1 999 Setup It is the setup screen to set the value less than 100 digit of the CT ratio This setup screen is only displayed on Ac...

Page 104: ...rent when it exceeds the maximum rating current Model Maximum rating current Three phase Accura 2350 3P 250A 105 250A Accura 2350 3P 125A 90 125A Accura 2350 3P 100A 75 100A Accura 2350 3P 60A 75 60A...

Page 105: ...want to set different threshold values in Accura 2350 modules you must set them individually through SET button on Accura 2350 Item Range Description ZCT threshold oFF d d d mA 1 Leakage current thres...

Page 106: ...1 25A 150A Accura 2350 1PSC 60A 50 0 40A 0 60A 72A 1 Single phase single phase single hole module meets 0 2 RD current accuracy and IEC62053 22 Class 0 5S power energy accuracy 2 Split core single ph...

Page 107: ...ue is not measured and is not displayed 2 The current and power indication of single phase power measuring module are displayed for 4 seconds to synchronize with three phase power measuring module dis...

Page 108: ...ID by default Module ID ID Description Communication ID ID 0 39 Able to communicate with Accura 2300 Conflict ID ID Duplication Two or more IDs are the same Module ID unable to communicate Standby ID...

Page 109: ...up 2011 Rootech Inc All Rights Reserved Page 109 Wiring Load Direction Setup Item Description VLN default Line to neutral wiring Load direction VLL Line to line wiring Load direction VLN Line to neutr...

Page 110: ...e 110 2011 Rootech Inc All Rights Reserved Phase Sequence Setup Depending on the selection in the Wiring load direction setup menu the setup range of Phase sequence setup menu is determined 1 Wiring l...

Page 111: ...Accura 2300 2350 User Guide Chapter 3 Accura 2350 Operation Setup 2011 Rootech Inc All Rights Reserved Page 111 2 Wiring load direction VLL Right load Line to line wiring Item Description...

Page 112: ...Chapter 3 Accura 2350 Operation Setup Accura 2300 2350 User Guide Page 112 2011 Rootech Inc All Rights Reserved 3 Wiring load direction VLN Left load Line to neutral wiring Item Description...

Page 113: ...Accura 2300 2350 User Guide Chapter 3 Accura 2350 Operation Setup 2011 Rootech Inc All Rights Reserved Page 113 4 Wiring load direction VLL Left load Line to line wiring Item Description...

Page 114: ...cura 2350 1PSH 30A 35 30A Split core single phase Accura 2350 1PSC 250A 105 250A Accura 2350 1PSC 125A 60 125A Accura 2350 1PSC 60A 50 60A Leakage Current Threshold Setup Leakage current measurement i...

Page 115: ...surement is oFF leakage current event setup is invalid If leakage current event is set to on the event log is processed on Accura 2300 when the measured leakage current exceeds the threshold setup val...

Page 116: ...e single phase single hole power measuring module meets current accuracy 0 2 RD error and power energy accuracy IEC62053 22 Class 0 2S Display Mode Front Display Display ID Accura 2350 Module ID 1 A m...

Page 117: ...current value is not measured and is not displayed 2 The current and power indication of single phase power measuring module are displayed for 4 seconds to synchronize with three phase power measuring...

Page 118: ...ID by default Module ID ID Description Communication ID ID 0 39 Able to communicate with Accura 2300 Conflict ID ID Duplication Two or more IDs are the same Module ID unable to communicate Standby ID...

Page 119: ...up 2011 Rootech Inc All Rights Reserved Page 119 Wiring Load Direction Setup Item Description VLN default Line to neutral wiring Load direction VLL Line to line wiring Load direction VLN Line to neutr...

Page 120: ...tral wiring Single phase or three phase measurement is possible by installing a single phase module and selecting a line to neutral phase For three phase measurement three single phase modules or two...

Page 121: ...evice Refer to Chapter 4 Setup Mode Accura 2350 1P Group Device Setup for group device setup Single phase single hole three module group device for 3 phase 4 wire 3 phase 3 wire 1 3 Three phase measur...

Page 122: ...Reserved 2 Wiring load direction VLL Right load Line to line wiring Single phase module is installed and line to line wiring is selected to support line to line single phase measurement 2 1 Single pha...

Page 123: ...ing a single phase module and selecting a line to neutral phase For three phase measurement three single phase modules or two single phase modules are required and group device settings for them are a...

Page 124: ...evice Refer to Chapter 4 Setup Mode Accura 2350 1P Group Device Setup for group device setup Single phase single hole three module group device for 3 phase 4 wire 3 phase 3 wire 3 3 Three phase measur...

Page 125: ...Page 125 4 Wiring load direction VLL Left load Line to line wiring Single phase module is installed and line to line wiring is selected to support line to line single phase measurement 4 1 Single pha...

Page 126: ...current event is set or not The leakage current threshold can also be set through Accura 2300 LCD screen or communication Threshold via Accura 2300 are common to all Accura 2350s connected to Accura 2...

Page 127: ...factors connection PT event Ethernet communication RS 485 communication etc Event log mode Displays event logs of power quality such as dip and swell event logs LED Display 4 LEDs placed at the lower...

Page 128: ...sing the SETUP button enables LCD screen to move to setup mode In setup mode using Left Up Down Right ESC ENTER buttons enables confirmation of the information and modification Fig 4 3 Screen of Setup...

Page 129: ...MIN Minimum BC Line to line BC F Lower left LED CA Line to line CA POWER Power LED on LD Lead Power factor EVENT Event LED blinks LG Lag Power factor ETHERNET Ethernet LED blinks D MODULE 2 RS 485 com...

Page 130: ...Reserved Start up Time Accura 2300 needs 30 seconds for start up time During the time measurement values are not displayed on LCD screen Temperature Sensor Accura 2300 measures the side temperature o...

Page 131: ...0 Fig 4 7 Accura 2350 Module ID Selection at upper part of LCD Screen Button Operation Button Description Display Mode Press 1 Select display mode Module ID Selection Long press 2 Make the Module ID U...

Page 132: ...isplay Full Screen Accura 2300 displays measurements of one Accura 2350 Module ID UNIT ID Voltage Current Power Energy Voltage Frequency Current Power PF Demand Active Power Leakage current 1 Ethernet...

Page 133: ...al voltage and the measured value for each phase can be continuously checked Press Up button to move the screen in the opposite direction and view the measured values Fig 4 9 Voltage Current Power Ene...

Page 134: ...button These are sequentially displayed in the reverse order by pressing Up button Fig 4 11 Current Display Screen Power Power Factor Detailed information for power and power factor is displayed by re...

Page 135: ...wn button These are sequentially displayed in the reverse order by pressing Up button Net energy is the value obtained by subtracting delivered energy from received energy and sum power is the sum of...

Page 136: ...corresponding device that is connected to Ethernet port 2 are sequentially displayed by pressing Down button The information can be displayed reversely by pressing Up button If RSTP setup of Ethernet...

Page 137: ...2300 is not formed In this case as there is no alternative route if connected port is disconnected network disconnection occurs with adjacent Accura 2300 rIng Ring connection Ethernet loop including t...

Page 138: ...Long Press 2 Make the setup value possible to be changed blink Press Increase or decrease the value of the menu screen by using UP or DOWN button or Press Move to the next left or right digit of the...

Page 139: ...Leakage Event Mod ID Assign Mod ID A2350 Module ID Next Group 2CT Group 3CT Group A2350 1P Group DHCP RSTP TCP timeout NTP Server NTP Sync MAC Address Gateway Subnet Mask IP Ethernet Comm Storm Block...

Page 140: ...P3O connection PT Rating Ratio of primary and secondary line to line voltage ratio is used as conversion ratio for primary voltage Regardless of voltage connection for measurement always PT primary an...

Page 141: ...se 3 wire connection 3P3W PT Primary VAB Secondary V12 Fig 4 20 1 phase 3 wire connection 1P3W PT Primary VL12 Secondary V13 Neutral line is the center point between line1 and line2 Fig 4 21 1 phase 2...

Page 142: ...Connection Setup Type Description 3 phase 4 wire 3P4W Line to line voltage setup Line to neutral reference voltage 1 3 Line to line voltage setup value Line to neutral voltage setup Line to neutral re...

Page 143: ...rrent considering harmonic components Refer to Chapter 5 Phase Power Measurement for details Setup range Description Fund default Fundamental component calculation HarM Harmonic component calculation...

Page 144: ...ute power factor without sign Power Factor Display at No Load In case that apparent power is 0 no load state power factor is not deterministic by formula Configure power factor display for this case F...

Page 145: ...e to neutral 3P4W 1P3W 1P2W connection VL L Line to line 3P3W connection d d d d V kV Dip reference voltage Percentage In each voltage connection dip reference voltage is determined as follows Voltage...

Page 146: ...words end voltage can be configured at least 1 higher than start voltage If start voltage is configured higher than end voltage end voltage is automatically reconfigured 1 higher than start voltage Se...

Page 147: ...Line to neutral 3P4W 1P3W 1P2W connection VL L Line to line 3P3W connection d d d d V kV Swell reference voltage Percentage In each voltage connection swell reference voltage is determined as follows...

Page 148: ...rds end voltage can be configured at least 1 lower than start voltage If start voltage is configured lower than end voltage end voltage is automatically reconfigured 1 lower than start voltage Setup r...

Page 149: ...cura 2300 side temperature sensor is different from the actual temperature in the distribution panel due to temperature difference of the measured value depending on the number of Accura 2350 connecte...

Page 150: ...lower than start temperature Setup range Description 0 9998 default 48 End temperature Current Event When the current event is set to on the screens that configure start current end current and curre...

Page 151: ...ent is generated when the measured current goes above start current and maintains upward status for exceeding current delay time Setup range Description 0 1 999 sec default 1 sec Current delay time se...

Page 152: ...time second 0 setup Leakage current delay time is 0 5 second Commonly applied to all Accura 2350s Individual setup for each module can be done in each Accura 2350 module Demand Current Event When the...

Page 153: ...ference power 1 Reference power for percentage is obtained by multiplying rating voltage by rating current for each Accura 2350 Commonly applied to all Accura 2350s 1 Reference power is as follows Vol...

Page 154: ...same as that shown in the start power Power Delay Time Power start event is generated if the measured power goes above the start power and maintains upward status for exceeding power delay time Delay...

Page 155: ...ule after this in the display mode this is indicated by blinking UNIT segment on the upper left Module ID ID Description Communication ID ID 0 39 Able to communicate with Accura 2300 Conflict ID ID Du...

Page 156: ...in order of connection to RJ12 2 port Assigned standby ID Auto assigned module ID RJ 2 Inc2 Auto assign 1 Module ID with standby ID 2 by 2 increment 0 2 4 in order of connection to RJ12 2 port Auto a...

Page 157: ...in order of connection to RJ12 2 port Assigned standby ID Auto assigned Module ID RJ 2 Inc1 Auto assign 1 Module ID with standby ID 2 by 1 increment 0 1 2 N in order of connection to RJ12 2 port Auto...

Page 158: ...ccura 2300 2350 User Guide Page 158 2011 Rootech Inc All Rights Reserved StbY Standby Assign all Accura 2350s as standby ID 1 Assigned specific Module ID Assigned standby ID 1 All Accura 2350s are fac...

Page 159: ...ignated as phase A In this case module IDs of the modules designated as phase B and C are not used When set as a three phase group device the wiring load direction setup of all modules of A B C phase...

Page 160: ...he wiring load direction on phase A module of Accura 2350 group device a 00 Assign module ID 0 to phase A module b 28 Assign module ID 28 to phase B module c 29 Assign module ID 29 to phase C module M...

Page 161: ...evice Setup of phase A module Set the wiring load direction on phase A module of Accura 2350 group device a 00 Assign module ID 0 to phase A module c 29 Assign module ID 29 to phase C module Module ID...

Page 162: ...ption 000 000 000 000 255 255 255 255 IP address default 010 010 010 100 Subnet Mask Setup range Description 255 255 000 000 255 255 255 252 Subnet mask default 255 255 255 000 Gateway Setup range Des...

Page 163: ...ress and hold ENTER button again to stop Sync blinking Time Sync is complete NTP Server Enter NTP Network Time Protocol server IP address for time synchronization of Accura 2300 Setup range Descriptio...

Page 164: ...cura 2300 2350 User Guide Page 164 2011 Rootech Inc All Rights Reserved DHCP Setup range Description oFF default DHCP disable on DHCP enable Storm Blocking Setup range Description oFF default Storm bl...

Page 165: ...s 4800 4800 bps 9600 default 9600 bps 19200 19200 bps 38400 38400 bps 57600 57600 bps 11520 115200 bps Parity bit Setup range Description EuEn default Even Parity nonE None Parity odd Odd Parity Stop...

Page 166: ...ser Guide Page 166 2011 Rootech Inc All Rights Reserved RS 485 Communication map Setup range Description a2300 default Accura 2300 Map r050 RTM050 Map If RS 485 communication map is set to r050 it is...

Page 167: ...d Reset Setup range Description dMd rESEt Demand reset Maximum Minimum Reset Setup range Description Max Min rESEt Maximum Minimum reset Peak Demand is also reset Energy Reset Setup range Description...

Page 168: ...lse on time Output type Command Operation 3 Latch 1 Maintain Closed contact 0 Maintain open contact Uncountable pulse 1 Pulse generation of single closed contact After the pulse is generated the comma...

Page 169: ...e the same ON state is maintained 1 d decimal number Pulse On time This menu screen is displayed only in the case that uncountable pulse countable pulse periodic pulse type is selected in Digital Outp...

Page 170: ...ault No selection dIP Dip Dip start event interlocking SueLL Swell Swell start event interlocking F FaIL Fuse Fail Fuse Fail start event interlocking Ph oPn Phase Open Phase open start event interlock...

Page 171: ...gy parameters are as follows Setup range Description no No Parameter default No selection r Wh Received active energy interlocking d Wh Delivered active energy interlocking r Urh Received reactive ene...

Page 172: ...hen DO polarity is Normal 0 Open contact operation 1 Closed contact operation When DO polarity is Reverse 0 Closed contact operation 1 Open contact operation DI Channel 1 Event Accura 2300 supports 2...

Page 173: ...to display the same display screen The table below is based on three phase measurement module Setup range Description rot default Rotation display ID Phase Current Power Three phase Current Average Po...

Page 174: ...e Setup range Description o OFF 0 9999 min default o OFF Setup of EVENT LED blink time when an event occurs o OFF blink time 0 blink time 5sec d d d d blink time 1 9999 min When the start event occurs...

Page 175: ...175 Event Blink On time Setup range Description 0 1 10 0 sec default 0 5 sec Setup of blink on time Demo Setup range Description oFF default Demo off baL 3 phase Balance demo on UnbaL 3 phase Unbalanc...

Page 176: ...n manufacturing steps and the user can only confirm it Serial Number Display Description Sn Product serial number d d 1 d d d d d d d d 1 d decimal number Hardware Version Display Description d d d 1...

Page 177: ...l start event occurs the Dip Swell segment on the top bar blinks When the end event occurs only the event log is processed and no alarm is generated The maximum 100 event logs are displayed Note Event...

Page 178: ...Press 2 Enter event log mode the newest event log is first displayed Press Select the event log or Long Press Move to the newest event log Long Press Exit event log mode and move to display mode 1 Whe...

Page 179: ...xisting event logs assigned from E777 to E678 Event Log E678 E777 Event Log E679 E778 E000 Start number of event log E000 Start number of event log E001 E001 E677 E677 E678 Event log N 99 1 E678 E679...

Page 180: ...d d d d d Dip event duration time msec 1 Phase or line to line in which the event occurred Phase A B C in 3P4W Line to line AB BC CA in 3P3W wiring Swell Event Log Swell Start Event Log Display Descr...

Page 181: ...d Event log number 000 999 A FuSE Fuse fail end event generation in phase A 1 End End event d d d d d Fuse fail event duration time msec 1 Phase in which the event occurred Temperature Event Log Temp...

Page 182: ...phase A 1 d d d d A Maximum current in the event duration A d d d d d Current event duration time msec 1 Phase in which the event occurred Leakage Current Event Log Leakage Current Start Event Log Dis...

Page 183: ...e B 1 d d d d A Demand current at start event A 1 Phase in which the event occurred Demand Current End Event Log Display Description E d d d Event log number 000 999 B dMd E Demand current end event g...

Page 184: ...etting element stops blinking when it is set to 3 phase 3 wire PT Rating Pt PT In the voltage connection Conn setup screen press Down button to move to the PT rating Pt setup screen A Pr Primary PT pr...

Page 185: ...le ID Auto Assignment IdSt ID Set Long press 2 SETUP button Go to setup mode Press Left or Right button to move to Accura 2350 Module ID Setup column Press Down button to move to the Module ID auto as...

Page 186: ...or Down to select the setting element from Stby Standby to RJ 2 RJ12 2 Inc2 Increment 2 Long press ENTER button set RJ 2 RJ12 2 Inc2 Increment 2 and blink stops auto assign all of Accura 2350s with m...

Page 187: ...press ESC button Exit setup mode and move to display mode 1 Press for more than 1 sec When the button is pressed Beep sounds And after one second Beep sounds again 2 cn Communication Accura 2300 comm...

Page 188: ...ss ENTER button the value that is possible to be changed blinks Increase or decrease the value of the menu screen by using Up or Down button Move to the next left or right digit of the value of the me...

Page 189: ...and minimum values after the reset provided by Accura 2300 are stored in the nonvolatile memory they are preserved even when Accura 2300 is turned off and then turned on The peak demand is initialized...

Page 190: ...reshed 1 cycle RMS voltage V Instantaneous Waveform 2 cycle voltage waveform 32 sample cycle V 2 cycle current waveform 32 sample cycle A 1 THD Total Harmonic Distortion Voltage THD 2 31 2 1 Current T...

Page 191: ...or Communication Event Parameters Phase Channel Total Start Event End Event Measured Value Measured Value Peak Value Duration Events of Accura 2300 and 2350 3P 1P Dip Swell Phase Open Fuse Fail Over C...

Page 192: ...ram Item Description V1 V2 V3 Line to neutral voltage sensing Line to neutral voltage V1 V2 V3 sensing based on wired N terminal voltage real line to neutral voltage VA V1 VB V2 VC V3 Line to line vol...

Page 193: ...nt can be detected by calculated residual current which is the sum of three phase currents Careful attention should be paid to small leak current judgments due to accuracy errors of CTs for each phase...

Page 194: ...rovided Item Line to neutral voltage rms Line to line voltage rms Current rms Active Power Phase A VA VAB IA I1 PA VA IA PFA Phase B VB VBC IB I2 PB VB IB PFB Phase C VC VCA IC I3 PC VC IC PFC Average...

Page 195: ...g Line to neutral voltage V1 V3 sensing based on N terminal voltage VA V1 VB 0 processed as zero by 1P3W setup VC V3 Line to line voltage calculation VAB 0 processed as zero by 1P3W setup VBC 0 proces...

Page 196: ...sensing Line to neutral voltage V1 sensing based on N terminal voltage VA V1 VB 0 processed as zero by 1P2W setup VC 0 processed as zero by 1P2W setup Line to line voltage calculation VAB VA VBC 0 pro...

Page 197: ...5 5 Half cycle Refreshed 1 cycle RMS Calculation Half cycle refreshed 1 cycle RMS 220 0 173 8 110 0 110 0 110 0 173 8 220 0 220 0 Dip Sag Swell Detection As it is defined in IEC 61000 4 30 Dip Sag Sw...

Page 198: ...he 1 cycle fundamental RMS value for every 1 cycle and provides the maximum value of these RMS values 30 60 Hz for every 0 5 second frame as the leakage current measurement value Residual Voltage Meas...

Page 199: ...phase is calculated by delaying the phase of the voltage by 90 degrees with respect to the fundamental frequency 1 4 0 where k a b c The apparent power for each phase is calculated by the magnitude of...

Page 200: ...ase sum is calculated As total apparent power varies the total power factor PF also varies Vector Sum Method Total apparent power is obtained by vector sum of 3 phase apparent powers The active power...

Page 201: ...Qc Sc Power Factor PF Measurement Power factor is calculated as the ratio of the effective power to the apparent power The sign of the power factor is a positive or negative value depending on the sig...

Page 202: ...e for the 4 quadrant voltage and current When the reactive power Q is 0 it is neither a LEAD state nor a LAG state Fig 5 9 Power Sign and PF Phase Angle Status P Q LAG LAG LEAD LEAD PF PF PF PF 0 0 0...

Page 203: ...10 Demand Calculation 1 35 Avg 3 0 Avg 4 0 Avg 4 8 Avg 4 3 Avg 2 5 Avg 2 6 1 20 1 25 1 30 1 40 1 45 demand output 3 93 4 37 3 87 3 0 4 0 4 8 3 4 0 4 8 4 3 3 4 8 4 3 2 5 3 time 1 15 3 20 2 6 3 0 4 0 3...

Page 204: ...e to line voltage that deviates most from the average voltage of the three phase line to line voltage If the magnitude of the phase voltage is the same and the phase is unbalanced the phase voltage un...

Page 205: ...negative sequence zero sequence Zero sequence component U0 Same component Positive sequence component U1 Symmetrical component for phase sequence A B C Negative sequence component U2 Symmetrical comp...

Page 206: ...ed by adding the aggregation start time and the difference time of the time stamp Fig 5 13 Aggregation Process Fixed aggregation Accura 2300 provides six aggregations from aggregation 1 through 6 with...

Page 207: ...2 66 seconds 0 9999 Aggregation 12 default 15 minute 12 180 minutes 0 9999 Aggregation 13 default 2 hour 10 20 hours 0 9999 Aggregation 14 default 12 hour 10 120 hours 0 9999 Aggregation 15 default 1...

Page 208: ...e 2 Channel Dry contact Common Ground Wire 1 5 to 3 5 mm2 16 to 12 AWG Rating DC 5V Self excitation Isolation Maximum 300V Min Pulse Width 1sec Digital Output 8 Connector type Terminal block DO DOG Wi...

Page 209: ...ral Weight 550g 1 Because of input voltage level of the device when using an external PT the primary voltage is the product of the PT ratio 2 Pulse is defined as pulse period and pulse on time 3 Conne...

Page 210: ...ingle phase Accura 2350 1PSH 50A 35 50mA 0 20A 60A single hole Accura 2350 1PSH 30A 35 30mA 0 12A 36A Impedance Not applicable because it is through hole structure Frequency range 42 69Hz Hole diamete...

Page 211: ...Frequency range 42 69Hz Hole size Model Size Weight through hole Three phase Accura 2350 3PSC 250A 105 23 0 x 31 7 mm 428g Accura 2350 3PSC 125A 90 18 2 x 31 7 mm 390g Accura 2350 3PSC 60A 75 13 4 x...

Page 212: ...ugh hole Accura 2350 1PSCSH 800A 43 9 x 45 1 mm 569g Accura 2350 1PSCSH 630A 33 5 x 41 2 mm 383g Accura 2350 1PSCSH 400A 33 5 x 41 2 mm 383g 1 Current accuracy meets 0 2 RD error and power energy conf...

Page 213: ...e ESD immunity IEC61000 4 3 Radiated radio frequency electromagnetic field immunity IEC61000 4 4 Electrical fast transient burst immunity IEC61000 4 5 Surge immunity IEC61000 4 6 Immunity to conducted...

Page 214: ...FS Current 0 0 999 9 0 5 FS TDD Current 0 0 999 9 0 5 FS Crest factor 4 0 0 999 9 0 5 FS K factor 4 0 0 999 9 0 5 FS 1 It is the RD error for the maximum phase voltage phase current in the three phase...

Page 215: ...30A 800A Reliability IEC61326 Electrical Equipment for Measurement Control and Laboratory EMC Standard Compliance Accura 2300 2350 IEC61000 4 2 Electrostatic discharge ESD immunity 4kV 8kV contact air...

Page 216: ...P 125A 090 Accura 2350 3P 100A 075 Accura 2350 3P 060A 075 Accura 2350 3P CT5A 075 Accura 2350 1P 250A 105 Accura 2350 1P 125A 060 Accura 2350 1P 100A 050 Accura 2350 1P 060A 050 Accura 2350 1P 50A 35...

Page 217: ...050L TM 1P 050 TM 3P 105 LB 1 TM 3P 90 LB 1 TM 1P 105 LB 1 TM 1P 60 LB 1 TM 1P 50L LB 1 TM 1P 50 LB 1 1 LB Long Busbar Special Purpose Modules Accura 2350 Type Range Description Accura 2350 GAS GAS M...

Page 218: ...ura 2350 3P 250A 105 TM 3P 105 Accura 2350 1P 250A 105 TM 1P 105 Accura 2350 3P 125A 90 TM 3P 90 Accura 2350 1P 125A 60 TM 1P 60 Accura 2350 3P 100A 75 TM 3P 75L Accura 2350 1P 100A 50 TM 1P 50L Accur...

Page 219: ...core Single phase Single hole Power Measuring Module Accura 2350 3PSC 250A 105 Accura 2350 1PSC 250A 105 Accura 2350 1PSCSH 800A Accura 2350 3PSC 125A 90 Accura 2350 1PSC 125A 60 Accura 2350 1PSCSH 63...

Page 220: ...Special purpose Module Accura 2350 GAS Accura 2350 GW Accura 2350 TEMP Accura 2350 DO Accura 2350 IDC Accura 2350 VDC Accura 2350 DCM...

Page 221: ......

Page 222: ...31 695 7350 Fax 82 31 695 7399 www rootech com supervisor rootech com 2011 Rootech Inc All Rights Reserved Accura EMeter Accura 2300 2350 Accura 2300S 2350 Accura 2700 2750 Accura 3000 Accura 3300E A...

Reviews: