Setup range
Description
0.02 - 1.00 A [default 0.20 A]
Start leakage current
Commonly applied to leakage current measurements of all Accura 2350s.
Individual setup for each module can be done in each Accura 2350 module.
Leakage Current Delay Time
Leakage current start event is generated when measured leakage current goes above start leakage current
and maintains upward status for exceeding leakage current delay time.
Setup range
Description
0 - 999 sec [default 1sec]
Leakage current delay time[second]
0 setup: Leakage current delay time is 0.5-second.
Commonly applied to all Accura 2350s.
Individual setup for each module can be done in each Accura 2350 module.
Demand Current Event
When the demand current event is set to on, the screen that configures start demand current is displayed. If
the demand current event is set to off, setup screen moves to power event setup screen.
Setup range
Description
oFF[default]
Event off
on
Event on
Commonly applied to all Accura 2350s.
Start Demand Current
Demand current start event is generated when the measured demand current goes above start demand
current.
Setup range
Description
5.0 - 999.0 % [default 70.0%]
Start demand current percentage
Reference current for percentage is rating current for each Accura 2350.
Commonly applied to all Accura 2350s.