Accura 2300/2350 User Guide
Chapter 2 Installation
ⓒ
2011 Rootech Inc. All Rights Reserved
Page 73
Step 2: Accura 2300 Wiring
Accura 2300 Voltage Connection
Fig 2.46 Accura 2300 Voltage Connection
Voltage Input
Item
Description
Connector name
V
1
, V
2
, V
3
, V
N
Connector type
Terminal block
Wire
2.1 to 3.5 mm
2
[14 to 12 AWG]
Measuring range
1
[Accuracy guaranteed]
AC 60 - 600V direct L-L[Line-to-Line]
Minimum measurement
1
AC 5V direct L-N[Line-to-Neutral]
Maximum measurement
1
AC 660V direct L-L[Line-to-Line]
Frequency range
50/60Hz, 42 - 69Hz
Voltage connection
3-Phase 4-Wire, 3-Phase 3-Wire, 1-Phase 3-Wire, 1-Phase 2-Wire connection
Burden
0.02VA/phase @ 220V
Withstand voltage
AC 2,000V RMS, 60Hz for 1minute
Impedance
3M
Ω
/phase
Compliance
Category
Ⅲ
1. Because of input voltage level of the device, when using an external PT, the primary voltage is the product of the PT ratio.
Note
If voltage input is out of the measurement range, the accuracy may be affected. For voltages greater than the
voltage input specification, an external PT[Potential Transformer] should be used.
Warning
When an external PT is used, a fuse should be mounted on the secondary side.