Accura 2300/2350 User Guide
Chapter 4 Accura 2300 Operation/Setup
ⓒ
2011 Rootech Inc. All Rights Reserved
Page 147
Swell Event
In case of configuring Swell event as “on”, the screen that configures Swell start voltage and Swell end voltage
are displayed. In case of configuring Swell event as “oFF”, the screen immediately moves to reference voltage
percentage setup screen.
Setup range
Description
oFF[default]
Event off
on
Event on
Swell Start Voltage
Swell start voltage is configured as a percentage to reference voltage. Swell start event is generated when the
measured voltage goes above start voltage.
Setup range
Description
102.0 - 999.0% [default 110.0%]
Percentage of Swell reference voltage
Swell start voltage display
VL-N [Line-to-neutral]
3P4W/1P3W/1P2W connection
VL-L[Line-to-line]
3P3W connection
[d][d][d].[d] V/kV
Swell reference voltage * Percentage
In each voltage connection, swell reference voltage is determined as follows.
Voltage Connection
Setup Type
Description
3-phase 4-wire[3P4W]
Line-to-line voltage setup
Line-to-neutral reference voltage
=
1 √3
⁄
* Line-to-line voltage setup value
Line-to-neutral voltage setup
Line-to-neutral reference voltage
= 1* Line-to-neutral voltage setup value
3-phase 3-wire[3P3W]
Line-to-line voltage setup
Line-to-line reference voltage
= 1* Line-to-line voltage setup value
1-phase 3-wire[1P3W]
Line-to-line voltage setup
Line-to-neutral reference voltage
=
1 2
⁄
* Line-to-line voltage setup value
Line-to-neutral voltage setup
Line-to-neutral reference voltage
= 1* Line-to-neutral voltage setup value
1-phase 2-wire[1P2W]
Line-to-neutral voltage setup
Line-to-neutral reference voltage
= 1* Line-to-neutral voltage setup value