Accura 2300/2350 User Guide
Chapter 4 Accura 2300 Operation/Setup
ⓒ
2011 Rootech Inc. All Rights Reserved
Page 145
Event Setup
Dip Event
In case of configuring Dip event as “on”, the screen that configures Dip start voltage and end voltage are
displayed. In case of configuring Dip event as “oFF”, the screen immediately moves to Swell event setup
screen.
Setup range
Description
oFF[default]
Event off
on
Event on
Dip Start Voltage
Dip start voltage is configured as a percentage to reference voltage. Dip start event is generated when the
measured voltage goes below the start voltage.
Three-phase 4-wire
Setup range
Description
1.0 - 98.0% [default 90.0%]
Percentage of Dip reference voltage
Dip start voltage display
VL-N [Line-to-neutral]
3P4W/1P3W/1P2W connection
VL-L[Line-to-line]
3P3W connection
[d][d][d].[d] V/kV
Dip reference voltage * Percentage
In each voltage connection, dip reference voltage is determined as follows.
Voltage Connection
Setup Type
Description
3-phase 4-wire[3P4W]
Line-to-line voltage setup
Line-to-neutral reference voltage
=
1 √3
⁄
* Line-to-line voltage setup value
Line-to-neutral voltage setup
Line-to-neutral reference voltage
= 1* Line-to-neutral voltage setup value
3-phase 3-wire[3P3W]
Line-to-line voltage setup
Line-to-line reference voltage
= 1* Line-to-line voltage setup value
1-phase 3-wire[1P3W]
Line-to-line voltage setup
Line-to-neutral reference voltage
=
1 2
⁄
* Line-to-line voltage setup value
Line-to-neutral voltage setup
Line-to-neutral reference voltage
= 1* Line-to-neutral voltage setup value
1-phase 2-wire[1P2W]
Line-to-neutral voltage setup
Line-to-neutral reference voltage
= 1* Line-to-neutral voltage setup value