Accura 2350-1P Group Device Setup
Three-phase Group Assignment
Accura 2350-1PSCSH split-core single-phase single-hole power measurement module is specified as [A, B, C
phase] and designated as three-phase group to perform three-phase measurement. The three-phase group
number is automatically assigned from 1 to 10 and is a number for identifying group devices.
Note
Module
ID
of three-phase group device is that of the module designated as phase A. In this case module IDs
of the modules designated as phase B and C are not used. When set as a three-phase group device the
"wiring/load direction" setup of all modules of A, B, C phase is automatically changed to VLN[Line-to-neutral
voltage] direction, and load direction on the B and C phase is also changed to the load direction on A
phase.
Setup range
Description
noSEt[default]
Three-phase group not assigned.
3-phase 4-wire/3-phase 3-wire, 3 Module Through-hole Wiring
a.[d][d]
1
Phase A module ID (group ID)
b.[d][d]
Phase B module ID
c.[d][d]
Phase C module ID
Refer to page 160.
3-phase 4-wire/3-phase 3-wire, 2 Module Through-hole Wiring
a.[d][d]
Phase A module ID (group ID)
c.[d][d]
Phase C module ID
Refer to page 161.
1. d
decimal number.