Accura 2300/2350 User Guide
Chapter 2 Installation
ⓒ
2011 Rootech Inc. All Rights Reserved
Page 81
Step 3: Accura 2350 Current Through-hole Wiring
Accura 2350 Three-phase[Single-phase] Power Measuring Module Through-hole Wiring
Accura 2350-3P[1P] Power Measuring Module Current Input
Item
Description
Connector type
Through-hole
Wire
Selection according to through-hole size
Measuring range
Model
Minimum
Measurement
Measuring Range
[Accuracy guaranteed
3
]
Three-phase
Accura 2350-3P-250A-105
250mA
1A -
300A
Accura 2350-3P-125A-90
125mA
500mA -
150A
Accura 2350-3P-100A-75
100mA
400mA -
120A
Accura 2350-3P-60A-75
60mA
240mA -
72A
Accura 2350-3P-CT5A-75
1
CT5mA
CT20mA -
CT6A
2
Single-phase
Accura 2350-1P-250A-105
250mA
1A -
300A
Accura 2350-1P-125A-60
125mA
500mA -
150A
Accura 2350-1P-100A-50
100mA
400mA -
120A
Accura 2350-1P-60A-50
60mA
240mA -
72A
Accura 2350-1P-50A-35
50mA
200mA -
60A
Accura 2350-1P-30A-35
30mA
120mA -
36A
Single-phase
Accura 2350-1PSH-50A-35
50mA
200mA -
60A
single-hole
Accura 2350-1PSH-30A-35
30mA
120mA -
36A
Impedance
Not applicable because of through-hole structure
Frequency range
42 - 69Hz
Hole diameter
Model
Size
Weight
[through-hole]
Three-phase
Accura 2350-3P-250A-105
Ф
21.0mm
217g
Accura 2350-3P-125A-90
Ф
16.5mm
196g
Accura 2350-3P-100A-75
Ф
13.5mm
155g
Accura 2350-3P-60A-75
Ф
13.5mm
155g
Accura 2350-3P-CT5A-75
1
Ф
13.5mm
155g
Single-phase
Accura 2350-1P-250A-105
Ф
21.0mm
217g
Accura 2350-1P-125A-60
Ф
16.4mm
99g
Accura 2350-1P-100A-50
Ф
13.5mm
85g
Accura 2350-1P-60A-50
Ф
13.5mm
85g
Accura 2350-1P-50A-35
Ф
8.9mm
74g
Accura 2350-1P-30A-35
Ф
8.9mm
74g
Single-phase
Accura 2350-1PSH-50A-35
Ф
9.0mm
71g
single-hole
Accura 2350-1PSH-30A-35
Ф
9.0mm
71g
1. If rating current exceeds 250A, Accura 2350-3P-CT5A-75 using external CT[secondary rating 5A] should be used.
2. Indicates CT secondary current input range.
3. Current accuracy meets ± 0.2% RD error and power/energy conforms to IEC62053-22 Class 0.5S.