User Manual – EC II GSM SE 

11 

identify EC II GSM SE in an alarm centre. It is also possible to have an SMS sent together or 
instead of the speech connecting alarm. 

5.2.1.2 

Programming 

The rear side of the speech unit has a keypad for programming call numbers, function selec-
tion and testing. There are also connectors for the central  unit,  an  alarm button  and  two  ex-
ternal  illuminated  pictograms.  All  settings  are  made  during  the  installation  and,  normally,  no 
subsequent changes are required. It is however also possible to program the EC II GSM SE 
remotely via SMS. 

5.2.1.3 

Incoming calls 

To contact possible trapped persons there is the possibility to phone in to the EC II GSM SE. 
Normally  it  is  open  for  incoming  calls  but  the  function  can  be  shut  down  or  programmed  so 
that it only allows incoming calls only after a lift alarm has occurred. 

5.2.1.4 

Power supply 

The  built-in  emergency  power  supply  monitors  and  tests  the  battery  regularly.  If  the  battery 
becomes bad and needs to be replaced, a battery alarm is sent to an alarm receiver. It is also 
possible  to  manually  reset  a  battery  alarm  with  a  button  on  the  printed  circuit  board  on  the 
central unit. The product cannot be used without a mounted and connected battery. 

5.2.1.5 

Emergency light 

It is possible to connect the lift’s emergency light to EC II GSM SE, which automatically turns 
the  light  on  when  the  mains  power  is  cut  off. When  the  mains  return  the  emergency  light  is 
switched  off.  In  the  central  unit  there  is  a  12V  DC  output,  which  can  be  used  for  external 
equipments such as an alarm bell or a loop amplifier for hearing impaired people. The output 
is connected to  voltage even after power failure, on the condition that the  emergency  power 
supply has not been disconnected from the battery to protect it against deep discharging. To-
gether  with  the  relay  output  on  central  unit,  these  two  outputs  can  be  used  for,  example,  to 
activate  an  external  alarm  bell.  The  relay  actuates  every  time  any  of  the  alarm  buttons  are 
activated but can also be activated remotely. 

5.2.1.6 

Intercom 

There is a possibility to connect an intercom telephone to the central unit for communications 
between  the  lift  car  and,  for  example,  the  machine  room  of  the  lift.  Most  telephones  can  be 
used, but they must be approved for connection to the public telephone network (TBR21 ap-
proved).  The  intercom  starts  when  telephone  receiver  is  lifted  and  finishes  when  the  tele-
phone  receiver  is  hung  up.  If  a  lift  alarm  should  occur  while  intercom  is  in  progress  the  lift 
alarm has priority and will disconnect the intercom. 

5.2.1.7 

Automatic test alarm 

EC II GSM SE can be set to send an automatic test alarm to a dedicated test alarm receiver 
with an interval of 1–9 days. The alarm is send soundlessly and tests the electronics and re-
ception quality of the EC II GSM SE If the test alarm should not occur, an alarm will be acti-
vated at the alarm centre and personnel can be sent to the lift to investigate and take care of 
possible defects. 

5.2.1.8 

Filtering 

To reduce the number of false alarms it is possible to connect EC II GSM SE with the control 
equipment of the lift to the filter input. Then it is possible to filter out all alarms attempts from 
the lift if the function is normal to reduce the workload on the alarm centre. For security rea-
sons no external alarm buttons (ALBU´s) are included by the filtering. 

Summary of Contents for EC II GSM SE

Page 1: ...EC II GSM SE User Manual...

Page 2: ...tionality 9 6 INSTALLATION 12 6 1 Installation of central unit 12 6 1 1 Installation of SIM card 14 6 1 2 Connection of battery 14 6 1 3 GSM antenna 14 6 1 4 Connection of speech unit 14 6 1 5 Alarm b...

Page 3: ...ut 27 8 4 11 Programmable alarm type 28 8 4 12 Change of security code 28 8 4 13 Change of alarm flashing sequence 28 8 4 14 Stop sending battery alarm 29 8 4 15 Relay control 29 8 4 16 End of alarm 2...

Page 4: ...red green yellow on the speech unit 45 14 FUSES IN CENTRAL UNIT 45 15 TROUBLESHOOTING 46 15 1 It is not possible to enter programming mode 46 15 2 F ltCom GSM SE does not make an alarm call 46 15 3 F...

Page 5: ...duced adapted or transcribed after written permission from copyright proprietor Copyright 2011 3 1 Warranty There is a 2 year warranty 24 months for manufacturing failure or material failure commenc i...

Page 6: ...freight charge The customer can ask for a quotation for repair of product not covered by warranty 4 General 4 1 Contents of packing Packing for EC II GSM SE contains following parts Central unit inclu...

Page 7: ...uZink See above Emergency power Battery 12V 2Ah Powered by Central unit Power supply 230V 0 1A 50 60Hz Powered by Central unit Indications Three LED One is two colored Yellow and green LED and sound P...

Page 8: ...6 Alarm button 2 ALBU 5 polig SPOX 2 50 mm Adapted for Part No 2122 7 Alarm button 3 ALBU 5 polig SPOX 2 50 mm Adapted for Part No 2122 8 Intercom 2 pol screw terminal block For standard telephone ac...

Page 9: ...ces where there are an explosion hazard On places where chemical substances are used in a greater extent with particu lar regard to safety rules for environments filled with unstable gases or fumes 5...

Page 10: ...wall or on ceiling of the lift car which eliminates the need to make holes other than those needed for the modular cable Intercon nection of the central unit and speech unit is very quick and simple s...

Page 11: ...r for hearing impaired people The output is connected to voltage even after power failure on the condition that the emergency power supply has not been disconnected from the battery to protect it agai...

Page 12: ...ust be able to receive the alarm type that is used for technical alarms 6 Installation Only competent and qualified personnel may install the EC II GSM SE Knowledge technical skill and correct equipme...

Page 13: ...ed which is intended to be used by the EC II GSM SE It is also possible to mount the central unit in the machinery room if no good GSM signal is available on the lift car roof Then the modular cable b...

Page 14: ...e EC II GSM SE Damages caused by incorrect battery types are not covered by warranty 6 1 3 GSM antenna The enclosed antenna is mounted in intended position in the chassis antenna contact on the extern...

Page 15: ...put is protected with fuse as protection against possible short circuit see section 14 below 6 1 7 Intercom For communications between lift machine room and the lift car there is a possibility to conn...

Page 16: ...M SE to the con trol equipment of the lift via the built in filter input By letting the lift decide if lift alarm should dial out the number of false alarms can be reduced For this function the contro...

Page 17: ...be drilled next to those of the edges of the frame see the enclosed drill template Mounting of speech unit in the enclosed frame 6 2 3 Recessed mounting There is also a possibility to mount the speech...

Page 18: ...al Unit One end of the enclosed modular cable is connected to socket in the central unit and the other end is connected to the speech unit input marked COM See picture above 7 Emergency power supply E...

Page 19: ...button S1 on the printed circuit board of the central unit is used It will recharge the new battery completely and test it The battery can operate the equipment for at least 60 minutes as long as the...

Page 20: ...tton S1 on the printed circuit board has been activated A battery reset command is sent via SMS If a battery is replaced after the EC II GSM SE has sent a battery alarm you should reset the battery al...

Page 21: ...ou change the EC II GSM SE at for example a repair no new programming is needed apart from the PIN code as long as the same SIM card as before is used The keys on the keyboard of the speech unit have...

Page 22: ...ically disconnected after 30 seconds if no key is pressed It is possible to manually exit the programming mode by pressing 8 3 Standard functions which must be programmed Below follows a description o...

Page 23: ...o the central unit alarm button input Reset the alarm button in the central unit to breaking function NC with Program the following when an alarm button of closing type NO is connected to the speech u...

Page 24: ...hes secondary receivers use the keypad on the back of the speech unit Check that the alarm reaches alarm receiver 2 by pressing programming mode EC II GSM SE immediately leaves the programming mode an...

Page 25: ...m button You can change the time that the alarm button must be pressed down before an alarm is acti vated The default time is 5 seconds but this time may be changed between 1 and 30 sec onds Note that...

Page 26: ...gits Enter alarm code for battery alarm with Alarm code max 10 digits Test the battery alarm receiver function in programming mode by enter After completed programming mode the EC II GSM SE immediatel...

Page 27: ...IN code 8 4 10 Filter input To reduce the number of false alarms there is the possibility to connect EC II GSM SE to the control equipment of the lift via the built in filter input By letting the lift...

Page 28: ...nit can be changed Alarm type The alarm type shall always be entered decimal and with two digits 00 99 Note that also ALBU 1 and ALBU 2 will use this alarm type Reset to original alarm type 10d for th...

Page 29: ...tery is damaged or not mounted Even if the product is not allowed to call out battery alarm the LED will still indicate any eventual battery alarm 8 4 15 Relay control Default the relay in the central...

Page 30: ...Note that it is only possible to use this functionality on speech units with front plates of stainless steel If the COP version is mounted behind a lift wall it is normally not possible to activate th...

Page 31: ...ch unit not the green LED in the central unit Read more about the LED under section 13 below 8 4 19 Change of communication protocol Default the CPC protocol is used for communication between the lift...

Page 32: ...above 9 2 Retrieving the telephone number To be able to program EC II GSM SE via SMS one must have access to the telephone num ber If that is not the case it is possible to find out by in programming...

Page 33: ...y as separator before the parame ter value An SMS may not be longer than 160 characters If not all information fits in one sin gle SMS the programming may be split in several SMS Every SMS must start...

Page 34: ...off E 0 alarm filter input off 1 alarm filter input active high 2 alarm filter input active low FF 00 99 alarm type for central unit alarm input ALBU1 ALBU2 G 0 traditional flash sequence for LED in...

Page 35: ...655_09gg It has been up and running for 21 days 10 hours and 13 minutes The battery is on stand by charge and the current voltage is 12 123V Battery alarms are allowed to be called out and a battery...

Page 36: ...pressing the switch S1 Note that this is exactly the same thing as pressing S1 on site The recharge cycle will be restarted which means that a forced charged of the battery is started follow by a res...

Page 37: ...e when an alarm is trigged 3 Only an SMS is sent when an alarm is trigged For an SMS to be sent follow the three steps below 1 You must decide which types of alarm that will trigger an SMS 2 You must...

Page 38: ...ne SMS from lift phone The alarm message can max be 80 letters long The letter A to E after SF3 in the SMS answer explains which type of alarms that have the SMS functionality activated See above for...

Page 39: ...ot always accessible by default On some SIM cards this number must be entered manually Mount the SIM card in a standard mobile telephone enter the phone book and search for the correct settings If thi...

Page 40: ...nd End of alarm since these alarm types can be set manually see section 8 4 11 and 8 4 16 above 9 9 Remote reset of the lift phone In some cases a complete reset of the lift phone is desired This is a...

Page 41: ...larm button in speech unit alarm button in central unit ALBU 1 and ALBU 2 10 1 Alarms sent to a automatic alarm central It is recommended that all alarms from EC II GSM SE should be sent to a 24 7 man...

Page 42: ...opportunity with alarm calls Note that all alarm receivers should practice the alarm handling procedure 10 2 1 Acknowledging an alarm Acknowledge the alarm with 4 ACKNOWLEDGE A voice communication ca...

Page 43: ...to EC II GSM SE from a tone dialing phone or a mobile phone according to the following 1 Dial the number to the EC II GSM SE 2 EC II GSM SE answers after the first signal with a 4 tone 3 Press 4 to a...

Page 44: ...tes function of GSM module Flashing sequence Information Green short flash Module connected to GSM net Green fixed light Network problem SIM card problem 13 1 3 LED C Three colored LED red green yello...

Page 45: ...ress Green fixed light Speech connection intercom is in progress Red Green alternating Programming mode Red Green Red short flash Battery alarm Red alternating on off Network problem SIM card problem...

Page 46: ...verage in the lift shaft Try to move central unit or mount it standing to improve the position of the antenna Another type of antenna might possibly be used In worst case the GSM covering so bad that...

Page 47: ...Programming of phone number to primary alarm receiver Max 20 dig its 8 3 4 2 Phone No Programming of phone number to secondary alarm receiver Max 20 digits 8 3 4 3 Test of secondary alarm receiver 8 3...

Page 48: ...arm function X 8 4 1 24 Code Alarm code to test alarm receiver Max 10 digits 8 4 1 25 Phone No Phone number to battery alarm re ceivers Max 20 digits 8 4 5 26 Test of battery alarm receiver 8 4 5 27 D...

Page 49: ...de Unlocking of SIM card due to faulty entered PIN code Max 8 digits 8 4 9 44 Activation of filter input active high 8 4 10 45 Deactivation of filter input X 8 4 10 46 Activation of filter input activ...

Page 50: ...8d 8 4 16 59 Activation of reed switch X 8 4 17 60 Deactivation of reed switch 8 4 17 61 Relay remotely controlled 8 4 15 62 Relay controlled by alarm button X 8 4 15 63 Old code New code New code Cha...

Reviews: