7-8
Communications
SMC — Flex Bit Identification
Table 7.G Logic Status Word
Bit #
Status
Description
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
X
Enabled
1 — Control Power Applied
0 — No Control Power
X
Running
1 — Power Applied to Motor
0 — Power
not
Applied to Motor
X
Phasing
1 — ABC Phasing
0 — CBA Phasing
X
Phasing
Active
1 — 3-phase is valid
0 — No valid 3-phase detected
X
Starting
(Accel)
1 — Performing a Start Maneuver
0 — Not Performing a Start Maneuver
X
Stopping
(Decel)
1 — Performing a Stop Maneuver
0 — Not Performing a Stop Maneuver
X
Alarm
1 — Alarm Present
0 — No Alarm Present
X
Fault
1 — Fault Condition Exists
0 — No Fault Condition
X
At Speed
1 — Full Voltage Applied
0 — Not Full Voltage Applied
X
Start/
Isolation
1 — Start/Isolation Contactor Enabled
0 — Start/Isolation Contactor Disabled
X
Bypass
1 — External Bypass Contactor
Enabled
0 — External Bypass Contactor
Disabled
X
Ready
1 — Ready
0 — Not Ready
X
Option 1
Input
1 — Input Active
0 — Input Inactive
X
Option 2
Input
1 — Input Active
0 — Input Inactive
—
—
Bits 14 and 15 — Not Used