1-2
Product Overview
Operation
The SMC-Flex controller can operate standard squirrel-cage
induction motors rated 1…1250 A or Star-delta (wye-delta) type
motors rated 1.8…1600 A; up to 690V AC, 50/60 Hz. Depending
upon the controller type ordered, the control power input can range
from 100…240V AC to 24V AC/DC. Please verify voltage on
product, before applying power.
Modes of Operation (Standard)
Soft Start
①
This mode has the most general application. The motor is given an
initial torque setting, which is user-adjustable from 0…90% of locked
rotor torque. From the initial torque level, the output voltage to the
motor is steplessly increased during the acceleration ramp time. The
acceleration ramp time is user-adjustable from 0…30 seconds. If the
SMC-Flex controller senses that the motor has reached the up-to-
speed condition during the voltage ramp operation, the internal
bypass contactor will be pulled in.
Figure 1.1 Soft Start
➀
Kickstart is also available with Soft Start.
Percent Voltage
100%
Initial
Torque
Time in Seconds
Start
Run
Ramp Time
Current Limit
Summary of Contents for SMC-Flex
Page 1: ...USER MANUAL FOR SERIES B SMC Flex BULLETIN 150...
Page 4: ...Notes...
Page 30: ...1 22 Product Overview Notes...
Page 126: ...9 8 Troubleshooting...
Page 148: ...B 14 Parameter Information Notes...
Page 150: ...C 2 Renewal Parts Notes...
Page 156: ...E 2 Accessories Notes...