B-8
Parameter Information
Jam
Jam A Lvl
69
%FLC
0…1000
0
Allows the user to set an instantaneous over
current level (% of line FLC) that will cause an
Alarm. A zero value is the “off” setting.
Jam
Jam A Dly
70
Secs
0…99
0
Allows the user the ability to prevent some
nuisance Alarms by entering a delay period
that provides a window that the motor over
current condition must persist within for the
controller to Alarm.
Stall
Stall Delay
71
Secs
0.0…10.0
0
This feature allows the user to program the
amount of time beyond the initial start
maneuver for the motor to be at speed. A
setting of zero means that the stall detection
feature is disabled.
Ground
Fault
Gnd Flt Enable
72
Disable
Enable
Disable
Enables ground fault protection when used
with an external core balanced ground fault
sensor.
Ground
Fault
➁
Gnd Flt Level
73
Amps
1.0…5.0
➁
2.5
➁
Allows the user to set a current (core balance
current) that will cause a fault when the
current is above this value.
Ground
Fault
Gnd Flt Delay
74
Secs
0.1…250.0
0.5
Allows the user the ability to prevent some
nuisance faults by entering a delay period that
provides a window that the ground fault
condition must persist within for the controller
to fault.
Ground
Fault
Gnd Flt Inh Time
75
Secs
0…250
10
Allow the user the ability to disable/inhibit
ground fault protection for a selected time
when starting.
Ground
Fault
Gnd Flt A Enable
76
Disable
Enable
Disable
Enables a ground fault protection Alarm when
used with an external core balanced ground
fault sensor.
Ground
Fault
➁
Gnd Flt A Lvl
77
Amps
1.0…5.0
➁
2.0
➁
Allows the user to set a current (core balance
current) that will cause an Alarm when the
current is above this value.
Ground
Fault
Gnd Flt A Dly
78
Secs
0…250
10
Allows the user the ability to prevent some
nuisance Alarms by entering a delay period
that provides a window that the ground fault
condition must persist within for the controller
to Alarm.
PTC
PTC Enable
79
Disable
Enable
Disable
Enables PTC based over-temperature
protection when used with external PTC
sensors.
Phase
Reversal
Phase Reversal
80
Disable
Enable
Disable
Allows the user to prevent starting if the
incoming line phase sequence is not correct.
The incoming power lines are expected to be
in an ABC sequence. The controller will fault if
power lines are out of the ABC sequence.
Restart
Starts Per Hour
81
0…99
Limits the number of starts that can occur in a
one-hour period. This feature includes a
"sliding window" for the one-hour time
period.
Table B.1 Parameter List (Continued)
Group
Parameter
Name
Parameter
Number
Units
Min./
Max.
Default
Settings
Parameter Description
User
Settings
➁
The 625, 780, 970, and 1250 A units the min./max. is 5.0.…25 and the default value is 5.0 Amps.
Summary of Contents for SMC-Flex
Page 1: ...USER MANUAL FOR SERIES B SMC Flex BULLETIN 150...
Page 4: ...Notes...
Page 30: ...1 22 Product Overview Notes...
Page 126: ...9 8 Troubleshooting...
Page 148: ...B 14 Parameter Information Notes...
Page 150: ...C 2 Renewal Parts Notes...
Page 156: ...E 2 Accessories Notes...