3-12
Wiring
Control Terminal Designations
As shown in Figure 3.10, the SMC-Flex controller contains 24 control
terminals on the front of the controller.
Figure 3.10 SMC-Flex Controller Control Terminals
➀
RC Snubbers are required on loads connected to auxiliary.
➁
Do not connect any additional loads to these terminals. These “parasitic” loads may cause problems
with operation, which may result in false starting and stopping.
➂
External Bypass operates an external contactor and overload relay once the motor reaches full
speed. The SMC-FLEX overload functionality, diagnostics and metering are disabled when the
external bypass is activated. Proper sizing of the contactor and overload is required.
➃
Control power on units rated 625
…
1250 A is pre-wired internally, from terminal block CP1.
Terminal
Number
Description
Terminal
Number
Description
11
Control Power Input
➀➃
23
PTC Input
➁
12
Control Power Common
➀➃
24
PTC Input
➁
13
Controller Enable Input
➁
25
Tach Input
14
Control Module Ground
26
Tach Input
15
Option Input #2
➀➁
27
Ground Fault Transformer Input
➁
16
Option Input #1
➀➁
28
Ground Fault Transformer Input
➁
17
Start Input
➀➁
29
Aux. Contact #2
➀➂
18
Stop Input
➀➁
30
Aux. Contact #2
➀➂
19
Aux. Contact #1
➀➂
31
Aux. Contact #3
➀➂
20
Aux. Contact #1
➀➂
32
Aux. Contact #3
➀➂
21
Not Used
33
Aux. Contact #4
➀➂
22
Not Used
34
Aux. Contact #4
➀➂