7-4
Communications
Connecting the Human Interface Module to the Controller
Figure 7.1 shows the connection of the SMC-Flex controller to a
human interface module. Table 7.C provides a description of each
port.
Note: The SMC-Flex only supports the use of DPI communication
modules and DPI HIM LCD Modules. Scanport devices are
not supported by the SMC-Flex.
See Figure 3.14 on page 3-16 for the control wiring diagram that
enables start-stop control from a human interface module.
Figure 7.1 SMC-Flex Controller with Human Interface Module
Table 7.C Description of Ports
HIM Control Enable
To enable motor control from a connected human interface module,
follow the procedure below with the connected human interface
module’s programming keys.
The Bulletin 20-HIM LCD human interface modules with control
panels can start and stop the SMC-FLEX controller. However, the
factory default settings disable control commands other than Stop
through the serial communication port.
Port 5 — DPI
Communications
Port 2
Ports 2 and 3 when two
HIMs are connected with
a splitter
Port #
Description
1
Unused — not available for use
2
First 20-HIM connected to SMC-Flex
3
Second 20-HIM connected to SMC-Flex
5
DPI Communication Board port